Troubleshooting
4.9
DC Fan Lock
E7
Remote
Controller
Display
A fan motor or related error is detected by checking the high-voltage fan motor rpm being detected
Method of
by the Hall IC.
Malfunction
Detection
The fan does not start in 30 seconds even when the fan motor is running.
Malfunction
The system is shut down if the error occurs 16 times.
Decision
Clearing condition: Continuous run for about 5 minutes (normal)
Conditions
Fan motor breakdown
Supposed
Harness or connector disconnected between fan motor and PCB or in poor contact
Causes
Foreign matter stuck in the fan
Troubleshooting
Check No.15
Refer to P.151
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
the connector, or parts damage may occur.
Fan motor
connector disconnected?
NO
Foreign matters
in or around the fan?
NO
Get started.
Check No. 15
Check the outdoor unit PCB rpm
pulse input.
Pulse signal
inputted?
YES
YES
YES
NO
SiUS04-904
Turn off the power and
reconnect the connector.
Remove.
Replace the outdoor unit fan
motor.
Replace the outdoor unit
PCB.
(R7139)
111