Daikin FTXS09HVJU Service Manual page 128

Inverter pair wall mounted type h-series
Hide thumbs Also See for FTXS09HVJU:
Table of Contents

Advertisement

Troubleshooting
4.11.2 15/18/24 Class
EA
Remote
Controller
Display
The room temperature thermistor, the indoor unit heat exchanger thermistor, the outdoor
Method of
temperature thermistor and the outdoor unit heat exchanger thermistor are checked to see if they
Malfunction
function within their normal ranges in the operating mode.
Detection
Malfunction
A following condition continues over 1 minute after operating 10 minutes.
 Cooling / dry operation
Decision
Conditions
 Heating
 Connector in poor contact
Supposed
 Thermistor defective
Causes
 Outdoor unit PCB defective
 Four-way valve coil or harness defective
 Four-way valve defective
 Foreign substance mixed in refrigerant
 Refrigerant shortage
Service Diagnosis
(room temp. – indoor heat exchanger temp.) < –18°F (< –10°C)
(indoor unit heat exchanger temp. – room temp.) < –18°F (< –10°C)
SiUS04-904
117