SiUS04-904
4.16 CT or Related Abnormality
H8
Remote
Controller
Display
A CT or related error is detected by checking the compressor running frequency and CT-detected
Method of
input current.
Malfunction
Detection
Malfunction
The compressor running frequency is below 55 Hz and the CT input is below 0.1 V.
(The input current is also below 1.25 A.)
Decision
If this error repeats 4 times, the system is shut down.
Conditions
The error counter is reset if this or any other error does not occur during the following 60-minute
Power transistor defective
Supposed
Internal wiring broken or in poor contact
Causes
Reactor defective
Outdoor unit PCB defective
126
compressor running time (total time).
Troubleshooting
Service Diagnosis