Indoor Unit Pcb Abnormality - Daikin FTXS09HVJU Service Manual

Inverter pair wall mounted type h-series
Hide thumbs Also See for FTXS09HVJU:
Table of Contents

Advertisement

Troubleshooting
4.2

Indoor Unit PCB Abnormality

A1
Remote
Controller
Display
Evaluation of zero-cross detection of power supply by indoor unit.
Method of
Malfunction
Detection
Malfunction
When there is no zero-cross detection in approximately 10 continuous seconds.
Decision
Conditions
 Faulty indoor unit PCB
Supposed
 Faulty connector connection
Causes
Troubleshooting
Connector Nos. vary depending on models.
Note:
Wall Mounted Type
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
the connector, or parts damage may occur.
Connector connection check
(note).
Is it normal?
YES
Model Type
NO
Connector No.
Terminal strip~Control PCB
SiUS04-904
(R7130)
99