Note: When parameter 04 HW/SW Option is set to 0=HW this
parameter is read-only and its value is set by rotary switches. See
chapter
03 Module Baud rate
Indicates the baud rate of the ControlNet interface. The baud rate
is fixed to 5 MBit/s.
5 = 5 MBit/s
04 HW/SW Option
Defines the selection source of module MacID.
0 = selection of MAC ID via the rotary switches enabled.
1 = selection of MAC ID via parameter 02 and via the ControlNet
Object enabled (see chapter
ControlNet Object, Class
05 Stop Function
Defines the method for stopping the motor.
0 = Ramp stop: the motor decelerates along the active
deceleration ramp.
1 = Coast stop: the motor comes to a stop by coasting.
06 Output Instance
07 Input Instance
These parameters define the preferred output and input
assemblies respectively.
The instances 20, 70, 21 and 71 are so-called Drive Profile
instances as defined in the ControlNet specification (AC/DC Drive
profile). The instances 121 and 171 correspond to instances 21
and 71, but contain additional space for user-mapped data. The
instances 100, 101, 102 and 103 are so-called vendor-specific
instances as defined by ABB, i.e. the control word, status word,
speed reference and speed actual value are defined by the ABB
Drives communication profile.