Local Operation
Using Multiple Supplies
Positive-negative Supply
To obtain a positive-negative supply, connect the negative output terminal of one
supply to the positive output terminal of the second supply. See
positive output terminal of the first supply now provides a positive voltage relative
to the common connection. The negative output terminal of the second supply
provides the negative voltage. You can set the current limits independently. The
maximum current available in split supply operation is equal to the rated output of
the supplies.
Figure 3.5 Split Supply Operation of Multiple Supplies
58
CAUTION
!
To prevent possible damage to the supply, do not connect the remote program
return line of the negative supply to the common connection.
(Local sense lines shown are default J2 connections.)
Figure
Positive-Negative Supply
Operating Manual for XHR Series Power Supply
3.5. The