Local Operation
Using Multiple Supplies
Two Positive Voltages To obtain two positive voltages, connect the negative
output terminals of both supplies together in a common connection. The positive
output terminals will provide the required voltages with respect to the common
connection. See Figure 3.4.
Figure 3.4 Split Supply Operation of Multiple Supplies
Positive-negative Supply
To obtain a positive-negative supply, connect the negative output terminal of one
supply to the positive output terminal of the second supply. The positive output
terminal of the first supply then provides a positive voltage relative to the common
connection while the negative output terminal of the second supply provides a
negative voltage. You can set the current limits independently. The maximum current
available in split supply operation is equal to the rated output of the supplies. For
example, 70 A for two 40 V, 70 A models. See Figure 3.5.
68
(Two Positive Voltages)
(Local sense lines shown are default J10 connections.)
CAUTION
!
To prevent possible damage to the supply, do not connect the remote program
return line of the negative supply to the common connection.
Operating Manual for XFR 2.8kW Series Power Supply