Figure 2.8 Multiple Loads With Local Sensing - Xantrex XHR 7.5-130 Operating Manual

Xhr 1000 watt series programmable dc power supply
Table of Contents

Advertisement

Installation
Load Connection
Radial Power Distribution Method To connect distributed loads, we
recommend that you use radial power distribution. With this method, you connect
power to each load individually from a single pair of terminals designated as the
positive and negative distribution terminals. These terminals may be the power
supply output terminals, the terminals of one of the loads, or a distinct set of
terminals especially established for distribution use. Connect the sense leads to these
terminals to compensate for losses and minimize the effect of one load upon another.
Figure 2.8
multiple loads. Local sense lines shown are default J2 connections. Refer to
Remote Sensing

Figure 2.8 Multiple Loads with Local Sensing

46
and
Figure 2.9
show recommended load and sensing connections for
for how to ground the sense line shield.
Operating Manual for XHR Series Power Supply