2.3 Wiring the Power Inputs

The 6-contacts terminal block connector on the top panel of Industrial Managed Switch is used for two DC redundant power
inputs. Please follow the steps to insert the power wire. The PWR1 is 1(-) & 2(+) and PWR2 is 5(-) & 6(+) contact.
Remember: Tighten the wire-clamp screws for preventing the wires from loosing.

2.4 Wiring the Fault Alarm Contact

The fault alarm contacts are in the middle (3 & 4) of the terminal block connector as the picture shows below. Inserting the wires,
the Industrial Managed Switch will detect the fault status of the power failure, or port link failure (available for managed model).
The following illustration shows an application example for wiring the fault alarm contacts
1
2
Power 1
-
+
Figure 2-4: 6-Contacts of Terminal Block Connector
1. The wire gauge for the terminal block should be in the range between 12 ~ 24 AWG.
2. Performing any of the procedures like inserting the wires or tighten the wire-clamp
screws. Ensure the power is OFF to prevent to get an electric shock.
Insert the wires into the fault alarm contacts
3
4
5
Fault
Power 2
-
37
User's Manual of IGS-10020MT
6
+