Figure 2-4 shows the upper panel of the IGS-1000-8UP4X.
2.4 Wiring the Power Inputs
The 6-contact terminal block connector on the top panel of Industrial Ethernet
Switch is used for two DC redundant power inputs. Please follow the steps
below to insert the power wire.
When performing any of the procedures like inserting the wires
or tightening the wire-clamp screws, make sure the power is
OFF to prevent from getting an electric shock.
1. Insert positive and negative DC power wires into Contacts 1 and 2 for
Power 1, or Contacts 5 and 6 for Power 2.
Dual power input is required
for maximum PoE loading.
Refer to user's manual for
Max. Fault Alarm Loading: 24V, 1A
1 2 3 4 5 6
V1+
PWR1
Figure 2-4: IGS-1000-8UP4X Upper Panel
Max. Fault Alarm Loading: 24V, 1A
1 2 3 4 5 6
V1+
PWR1
more details.
DC Input:
V2+
48-54V
, 8A max.
Alarm
PWR2
DC Input: 9-48V
V2+
AC Input: 24V , 0.8A max.
Alarm
PWR2
, 2A max.
9