GE MULTILINK ML2400 Instruction Manual page 74

Ethernet communications switch
Hide thumbs Also See for MULTILINK ML2400:
Table of Contents

Advertisement

IP ADDRESSING
5–6
Inbound Telnet Enabled: Yes
Outbound Telnet Enabled: Yes
Web Console Enabled: Yes
SNMP Enabled: Yes
Terminal Type: VT100
Screen Refresh Interval (sec): 3
Baud Rate: 38400
Flow Control: None
Session Inactivity Time (min): 10
ML2400#
Users can telnet to a remote host from the MultiLink family of switches using the following
syntax.
telnet <ipaddress> [port=<port number>]
The default port for telnet is 23.
To start a telnet session through the EnerVista Secure Web Management software,
Select the Administration > Telnet menu item.
The default port for telnet is 23.
The ML2400 will time out an idle telnet session. It may be useful to see who is currently
connected to the switch. It may also be useful for a person to remotely terminate a telnet
session. To facilitate this, the ML2400 supports the following two commands:
show session
kill session id=<session>
For example:
user
ML2400#
useraccess user=peter service=telnet enable
ML2400(user)##
Telnet Access Enabled.
exit
ML2400(user)##
show session
ML2400#