MISCELLANEOUS COMMANDS
17–4
Example 17-1: Alarm relays
ML2400#
alarm
ML2400(alarm)##
add event=2
Alarm Event(s) Added: 2
ML2400(alarm)##
add event=1-5
Event 2 is Already Enabled.
Alarm Event(s) Added: 1, 3, 4, 5
ML2400(alarm)##
add event=6,8
Alarm Event(s) Added: 6, 8
ML2400(alarm)##
add event=all
Event 1 is Already Enabled.
Event 2 is Already Enabled.
Event 3 is Already Enabled.
Event 4 is Already Enabled.
Event 5 is Already Enabled.
Event 6 is Already Enabled.
Event 8 is Already Enabled.
Alarm Event(s) Added: 7, 9, 10, 11, 12
ML2400(alarm)##
del event=2
Alarm Event(s) Deleted: 2
ML2400
(alarm)## period time=5
Relay closure Time Set.
ML2400(alarm)##
show alarm
Alarm Events Configuration
--------------------------
Alarm Status: DISABLED
Relay Closure Time Period: 5 Seconds
EventId
Description
------------------------------------------
1
S-RING OPEN
2
Cold Start
3
Warm Start
4
Link Up
5
Link Down
6
Authentication Failure
7
RMON Raising Alarm
8
RMON Falling Alarm
9
Intruder Alarm
10
Link Loss Learn Triggered
11
Broadcast Storm Detected
12
STP/RSTP Reconfigured
(continued on next page)
MULTILINK ML2400 ETHERNET COMMUNICATIONS SWITCH – INSTRUCTION MANUAL
CHAPTER 17: MISCELLANEOUS COMMANDS
Mode
SUSTAINED
NOT ENABLED
MOMENTARY
MOMENTARY
MOMENTARY
MOMENTARY
MOMENTARY
MOMENTARY
MOMENTARY
MOMENTARY
MOMENTARY
MOMENTARY