HP StorageWorks MSL5000 series User Manual page 154

Tape libraries
Hide thumbs Also See for StorageWorks MSL5000 series:
Table of Contents

Advertisement

Troubleshooting
Table 11: Fault Symptom Codes (Continued)
FSC
3078
Diag get drive 0 status failed
(Failed to get drive status, communication
error.)
3079
Diag get drive 1 status failed
(Failed to get drive status, communication
error.)
307A
Diag get drive 2 status failed
(Failed to get drive status, communication
error.)
154
Message
HP StorageWorks MSL5000 and MSL6000 Series Tape Libraries User Guide
ERP
Press the Enter button to reboot.
Ensure the drive shows good status
through the drive status window.
Deactivate the drive using the GUI control
panel maintenance menu.
Reseat drive.
Load/unload a cartridge to the drive to
verify.
Check the tape cartridge used in the last
operation for damage.
Run the cartridge cycle diagnostic to
verify.
Press the Enter button to reboot.
Ensure the drive shows good status
through the drive status window.
Deactivate the drive using the GUI control
panel maintenance menu.
Reseat drive.
Load/unload a cartridge to the drive to
verify.
Check the tape cartridge used in the last
operation for damage.
Run the cartridge cycle diagnostic to
verify.
Press the Enter button to reboot.
Ensure the drive shows good status
through the drive status window.
Deactivate the drive using the GUI control
panel maintenance menu.
Reseat drive.
Load/unload a cartridge to the drive to
verify.
Check the tape cartridge used in the last
operation for damage.
Run the cartridge cycle diagnostic to
verify.