Mounting Procedure - Fuji Electric FEH300b Hardware User Manual

Display attached controller
Table of Contents

Advertisement

(1) Mounting procedure

1) Insert the @E.Terminal unit into the mounting panel (max. thick: 5 mm).
X
Y
2) Insert four fixtures attached to the @E.Terminal unit into the mounting holes, and tighten them with the
tightening screws.
Tightening torque: 0.5 to 0.7 N·m
Fixture dimensions
(Unit: mm)
10.5
17.8
* When the @E.Terminal unit is attached to the mounting panel, the fixtures and frame grounds (FG) are connected.
To prevent static electricity, be sure to connect the mounting panel to the frame ground.
3) Mount the gasket so that it will be sandwiched securely between the @E.Terminal unit and the mounting panel.
(2) Mounting angle
Install the unit within the angle of 15 to 135 as shown on the right.
Section 3 Installation
3-1 Mounting Procedure
Panel cut-out dimensions
Types
NP5M0101-5H4/NP5N0011-5H4
NP5M0101-4H4/NP5N0011-4H4
NP5M0101-3H4/NP5N0011-3H4
X
Y
ONL
ERR
SX-B US
UROM
RUN
ALM
IN
BAT
4:RUN
3:U-TERM
2:TERM
1:STOP
CPU
No.
OUT
DC24 V
0V
USB
FG
USER ROM
CARD
LOAD ER
3-1
Unit: mm
X
Y
+0.5
+0.5
313.0
246.2
-0
-0
+0.5
+0.5
289.0
216.2
-0
-0
+0.5
+0.5
220.5
165.5
-0
-0
90
135
15
0