6. Parameters 
6.1. Parameter Group 1 – Basic Parameters 
Par. 
Description 
Maximum 
P1‐01 
Frequency / Speed  
Minimum 
P1‐02 
Frequency / Speed 
Acceleration ramp 
P1‐03 
time 
Deceleration ramp 
P1‐04 
time 
P1‐05 
Stop mode select 
P1‐06 
Energy Optimiser 
Motor rated 
P1‐07 
voltage 
Motor rated 
P1‐08 
current  
Motor rated 
P1‐09 
frequency 
P1‐10 
Motor rated speed 
P1‐11 
Preset Speed 1 
Terminal / Keypad / 
PID  
P1‐12 
Drive Control Mode 
Selection 
P1‐13 
Trip log 
Extended menu 
P1‐14 
access  
 
NOTE 
Default parameter values for Horse Power rated drives are shown in brackets 
 
Following a factory reset, or when installing a drive for the first time, only Group 1 Parameter access is available. To allow access to Parameters 
Groups 0, 2, 3 and 4, Parameters P1‐14 and P2‐37 must contain the same value. The factory set value for P2‐37 = 101 
16 
www.invertek.co.uk 
 
Range 
P1‐02 to 5*P1‐09 (max 2000Hz) 
0 to P1‐01 
0 to 3000 
0 to 3000 
0 : Ramp to stop with brown‐
out ride‐through on mains loss 
1 : Coast to stop 
2 : Ramp to stop  with 'fast 
stop' on mains loss 
0: Disabled 
1: Enabled 
0, 20 to 250 
0, 20 to 500 
25% ‐100% of drive rated 
current 
25Hz to 2000Hz 
0 to 60 000 rpm 
‐P1‐01 to P1‐01  
0 : Terminal control 
1 : Keypad control – fwd only 
2 : Keypad control − fwd and 
rev 
3 : PID Control 
4 : Modbus RTU Control 
Last four trips stored 
Code 0 to 30000 
 
Units 
Default 
Explanation 
Hz 
50 
Maximum speed limit – Hz or rpm. 
Rpm 
(60) 
If P1‐10 >0, the value entered is in Rpm 
Hz 
Minimum speed limit – Hz or rpm. 
Rpm 
If P1‐10 >0, the value entered is in Rpm 
Acceleration ramp time from 0 to base speed (P1‐
seconds 
09) in seconds 
Deceleration ramp time from base speed (P1‐09) 
seconds 
to standstill in seconds.  When set to zero, fastest 
possible ramp time without trip is activated 
0 : When the drive enable signal is removed, the 
drive will ramp to stop at the rate set in P1‐04. If 
the mains supply is lost, the drive will try to 
continue running by reducing the speed of the 
load using the load as a generator. 
‐ 
1 : When the enable signal is removed from the 
drive, the motor will coast (freewheel) to stop 
2 :  When the drive enable signal is removed, the 
drive will ramp to stop at the rate set in P1‐04. If 
the mains supply is lost, the drive will ramp to stop 
using the P2‐25 decel ramp time 
When enabled, automatically reduces applied 
‐ 
motor voltage on light load. Minimum value is 50% 
of nominal rated voltage (P1‐07) 
230 
Rated (nameplate) voltage of the motor (Volts). 
Volts 
400 
Value limited to 250V for low voltage drives.  
(460) 
Drive 
Enter the rated (nameplate) current of the motor. 
Amps 
rating 
This value is used for overload protection 
50 
Enter the rated (nameplate) frequency of the 
Hz 
(60) 
motor 
When non‐zero, all speed related parameters are 
Rpm 
displayed in rpm. Enter the motor rated 
(nameplate) speed if this is required. 
50 
Sets the speed the drive runs at when Preset 
Hz / Rpm 
(60) 
Speed 1 is selected 
Primary Control Mode of the drive. 
0 : Terminal control 
1 : Uni‐directional keypad control.  Keypad START 
button does not reverse direction. 
‐ 
2 : Bi‐directional keypad control. Keypad START 
button toggles between forward and reverse. 
3 : User PID control with external feedback signal 
4 : Modbus RTU Control. See section 10 
Previous 4 trips stored in order of occurrence, with 
the most recent first.  
‐ 
Read only 
Press UP or DOWN to step through all four.   
The most recent trip is always displayed first.  
UV trip is only stored once. 
Set to "101" (default) for extended menu access.  
‐ 
Change code in P2‐37 to prevent unauthorised 
access to the Extended Parameter Set 
Optidrive Plus 3
GV
 User Guide 