Control Terminal Connections - Invertek Drives Optidrive Plus 3GV User Manual

Ip20 & enclosed ip55/nema 12 ac variable speed drive
Hide thumbs Also See for Optidrive Plus 3GV:
Table of Contents

Advertisement

4.7. Control terminal connections 
 
Default Connections 
 
4.8. Electromagnetic Compatibility 
All Optidrives are designed to high standards of EMC and can optionally be fitted with an internal EMC filter. This EMC filter is designed to reduce 
the conducted emissions back into the supply via the power cables for compliance with harmonised European standards. 
It is the responsibility of the installer to ensure that the equipment or system into which the product is incorporated complies with the EMC 
legislation of the country of use. Within the European Union, equipment into which this product is incorporated must comply with 89/336/EEC, 
EMC. When using the internal or optional external filter, the following maximum motor cable lengths apply:‐ 
 
 
 
EMC Category 
C1 
Drive Frame Size 
 
230 Volt, Single Phase Input 
Size 1 
1m 
Size 2 
1m 
3 Phase, 400 Volt Input 
Size 2 
5m 
Size 3 
5m 
Size 4 
5m 
Size 5 
5m 
Size 6 
5m 
For motor cable lengths greater than 100m, an output dv / dt filter must be used, please refer to the Invertek Stock Drives Catalog 
for further details 
For Size 5 and 6 drives, ferrite ring must be installed on the output motor cable, with all three phases of the motor cable being 
Note 
wrapped one turn around the ferrite ring. 
Vector Speed and Torque control modes may not operate correctly with long motor cables and output filters. It is recommended to 
operate in V/F mode only for cable lengths exceeding 50m 
GV
Optidrive Plus 3
 User Guide 
www.invertek.co.uk 
 
Control Terminal 
Signal 
+24V User 
Output, 
Digital Input 1 
Digital Input 2 / 
Digital Output 3 
Digital Input 3 / 
Analog Input 2 
+24V User Output 
Bipolar analog 
Input / 
Digital Input 4 
0V 
Analog Output / 
Digital Output 
0V 
 
10 
Relay Common 
11 
Relay NO Contact 
Screened Motor Cable Length 
With Internal Filter 
C2 
5m 
5m 
25m 
25m 
25m 
25m 
25m 
 
Description 
+24V, 100mA user control output 
Positive logic 
"Logic 1" input voltage range: 8V ... 30V DC 
"Logic 0" input voltage range: 0V ... 8V DC 
Input : Positive logic 
"Logic 1" input voltage range: 8V ... 30V DC 
"Logic 0" input voltage range: 0V ... 8V DC  
Output : 24V 10mA Max 'Drive Healthy' Output 
Digital : "Logic 1" input voltage range : 8 to 30V DC 
               "Logic 0" input voltage range : 0 to 8 V DC 
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA 
+24V, 100mA, 1kΩ minimum 
Digital : "Logic 1" input voltage range : 8 to 30V DC 
               "Logic 0" input voltage range : 0 to 8 V DC 
Analog: 0 to 24V, 0 to 10V, ‐10 to +10V, ‐24 to + 24V 
User ground, connected to terminal 9 
Analog: 0 to 10V DC, 10 to 0 V DC, 20mA Maximum 
                4 to 20mA, 20 to 4 mA 
Digital:  0 to 24V DC, 20mA Maximum 
User ground, connected to terminal 7 
Volt free contacts. Maximum load should not exceed 
250Vac, 6A / 30Vdc, 5A 
C3 
C1 
 
25m 
25m 
25m 
50m 
50m 
50m 
50m 
50m 
50m 
50m 
50m 
50m 
50m 
50m 
With External Filter 
C2 
50m 
100m 
100m 
200m 
100m 
200m 
100m 
200m 
100m 
200m 
100m 
200m 
100m 
200m 
 
 
 
C3 
11
 

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Optidrive Plus 3GV and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents