Analog And Digital Input Configurations; Terminal Mode (P1-12 =0) - Invertek Drives Optidrive Plus 3GV User Manual

Ip20 & enclosed ip55/nema 12 ac variable speed drive
Hide thumbs Also See for Optidrive Plus 3GV:
Table of Contents

Advertisement

7. Analog and Digital Input Configurations 
7.1. Terminal mode (P1‐12 =0) 
P2‐01 
Digital input 1 (T2) 
Open: Stop (disable) 
Closed: Run (enable) 
Open: Stop (disable) 
Closed: Run (enable) 
Open: Stop (disable) 
Closed: Run (enable) 
 
 
 
 
Open: Stop (disable) 
Closed: Run (enable) 
Open: Stop (disable) 
Closed: Run (enable) 
 
Open: Stop (disable) 
 
Closed: Run (enable) 
 
 
Open: Stop (disable) 
Closed: Run (enable) 
Open: Stop (disable) 
Closed: Fwd Run (enable) 
Open: Stop (disable) 
8  
Closed: Fwd Run (enable) 
Open: Stop (disable) 
Closed: Forward Run (enable) 
Open: Stop (disable) 
10 
Closed: Forward Run (enable) 
Open: Stop (disable) 
11 
Closed: Run (enable) 
Open: Stop (disable) 
12 
Closed: Run (enable) 
Normally Open (NO) 
13 
Momentarily Close to Run 
Normally Open (NO) 
14 
Momentarily Close to Run Fwd 
Open: Stop (disable) 
15 
Closed: Run (enable) 
Open: Stop (disable) 
16 
Closed: Run (enable) 
Normally Open (NO) 
17 
Momentarily Close to Run Fwd 
18 
 
Open: Stop (disable) 
 
Closed: Run (enable) 
 
 
Open: Stop (disable) 
19 
Closed: Run (enable) 
Open: Stop (disable) 
20 
Closed: Run (enable) 
Open: Stop (disable) 
21 
Closed: Run (enable) 
Open: Stop (disable) 
22 
Closed: Run (enable) 
 
Negative Preset Speeds will be inverted if Run Reverse selected. 
NOTE 
The external trip input can be used to connect a motor thermistor by connecting between terminals 1 and 4 
22 
www.invertek.co.uk 
 
Digital input 2 (T3) 
Open : Bipolar analog speed ref 
Closed : Preset speed ref 
Open: Preset Speed 1 
Closed: Preset speed 2 
Digital Input 2 
Digital Input 3 
Open 
Open 
Closed 
Open 
Open 
Closed 
Closed 
Closed 
Open 
Open 
Closed 
Open 
Open 
Closed 
Closed 
Closed 
Open : Forward 
Closed : Reverse 
Open : Forward 
Closed : Reverse 
Open : Forward 
Closed : Reverse 
Open : Forward  
Closed : Reverse 
Open: Stop (disable) 
Closed: Rev Run (enable) 
Open: Stop (disable) 
Closed: Rev Run (enable) 
Open: Stop (disable) 
Closed: Reverse Run (enable) 
Open: Stop (disable) 
Closed: Reverse Run (enable) 
Open : Bipolar analog speed ref 
Closed : Preset speed 1 
Open : Preset Speed 1 
Closed : Bipolar analog speed ref 
Normally Closed (NC) 
Momentarily Open to Stop 
Normally Closed (NC) 
Momentarily Open to Stop 
Open : Forward 
Closed : Reverse 
Open : Forward 
Closed : Reverse 
Normally Closed (NC) 
Momentarily Open to Stop 
Digital Input 2 
Digital Input 3 
Open 
Open 
Closed 
Open 
Open 
Closed 
Closed 
Closed 
Open : Bipolar analog speed ref 
Closed : Analog input 2 speed ref 
Digital Output : 
Drive Healthy = +24V 
Digital Output : 
Drive Healthy = +24V 
Digital Output : 
Drive Healthy = +24V 
 
Digital input 3 (T4) 
Open : Preset Speed 1 
Closed : Preset Speed 2 
Open: Preset speed 1 / 2 
Closed: Preset speed 3 
Bipolar analog input 
Open  
Open 
Open 
Open 
Closed 
Closed 
Closed 
Closed 
Open: Bipolar analog ref  
Closed: Preset Speed 1 
Analog input 2 
(E.g. Torque reference) 
Digital Input 3 
Bipolar analog input 
Open 
Open 
Closed 
Open 
Open 
Closed 
Closed 
Closed 
External trip input : 
Open: Trip,  
Closed: No Trip 
Open: Bipolar analog speed ref  
Closed: Preset Speed 1 
Open: Preset Speed 1 
Closed: Bipolar analog speed ref 
Digital Input 3 
Bipolar analog input 
Open 
Open 
Closed 
Open 
Open 
Closed 
Closed 
Closed 
External trip input : 
Open: Trip,  
Closed: No Trip 
External trip input : 
Open: Trip,  
Closed: No Trip 
External trip input : 
Open: Trip,  
Closed: No Trip 
Open: Bipolar analog speed ref  
Closed: Preset Speed 1 
Normally Open (NO) 
Momentarily Close to Run Rev 
Open: Decel Ramp 1 (P1‐04)  
Closed: Decel Ramp 2 (P2‐25) 
Open: Decel Ramp 1 (P1‐04)  
Closed: Decel Ramp 2 (P2‐25) 
Normally Open (NO) 
Momentarily Close to Run Rev 
Preset Speed Ref 
Preset Speed 1 
Preset Speed 2 
Preset Speed 3 
Preset Speed 4 
Analog input 2 
Open : Bipolar analog speed ref 
Closed : Preset Speed 1 
Open : Forward 
Closed : Reverse 
External trip input : 
Open: Trip,  
Closed: No Trip 
GV
Optidrive Plus 3
 User Guide 
Analog input (T6) 
Bipolar analog input   
Open : Preset Speed 1 / 2 / 3 
Closed : Preset Speed 4 
Speed Setpoint 
Preset Speed 1 
Preset Speed 2 
Preset Speed 3 
Preset Speed 4 
Preset Speed 5 
Preset Speed 6 
Preset Speed 7 
Preset Speed 8 
Bipolar analog input 
Bipolar analog input 
Speed Setpoint 
Preset Speed 1 
Preset Speed 2 
Preset Speed 3 
Preset Speed 4 
Bipolar analog input  
Bipolar analog input 
Bipolar analog input 
Preset Speed 
Preset Speed 1 
Preset Speed 2 
Preset Speed 3 
Preset Speed 4 
Bipolar analog input  
Bipolar analog input  
Bipolar analog input  
Bipolar analog input 
Bipolar analog input 
Bipolar analog input 
Open: Preset Speed 1 
Closed : Preset speed 2 
Open: Preset Speed 1 
Closed : Keypad Speed Ref 
Open : Preset Speed Ref 
Closed : Keypad Speed Ref 
Bipolar analog input 
Bipolar analog input 
Bipolar analog input 
Bipolar analog input 