10.5.
Modbus Register Map 
Register 
Par. 
Supported 
Type 
Number 
Commands 
‐ 
R/W 
‐ 
R/W 
‐ 
R/W 
‐ 
R/W 
‐ 
‐ 
 
 
P0‐13 
10 
 
11 
‐ 
21 
P0‐01 
22 
P0‐02 
40 
P0‐20 
41 
P0‐21 
42 
P0‐22 
43 
P0‐23 
44 
P0‐24 
45 
P0‐25 
46 
P0‐26 
47 
P0‐27 
Further registers are available; see the Optidrive Plus 3
32 
www.invertek.co.uk 
 
Function 
Low Byte 
03,06 
Drive Control Command 
03,06 
Modbus Speed reference setpoint 
03,06 
Torque reference 
03,06 
Acceleration and Deceleration Time  0..255 
03 
Reserved 
03 
Error code 
Drive status 
03 
Output Motor Frequency 
03 
Output Motor Current 
03 
Output Motor Torque  
03 
Output Motor Power 
03 
Digital input status 
03 
Bipolar analog input value 
nd
03 
2
 analog input value 
03 
DC bus voltage 
03 
Drive temperature 
03 
Supply voltage L1 
03 
Supply voltage L2 
03 
Supply voltage L3 
03 
Estimated rotor speed 
03 
kWh meter 
03 
MWh meter 
GV
 Advanced User Guide for details. 
 
Range 
Explanation 
High Byte 
0..3 
16 Bit Word.  
Bit 0 : Low = Stop, High = Run Enable 
Bit 1 : Low = No Function, High = Fault Reset 
Bit 2 : Low = Decel Ramp 1 (P1‐04), High = Decel Ramp 2 
0..20000  Setpoint frequency x10, e.g. 100 = 10.0Hz 
0..2000 
Torque Setpoint %x10, e.g. 1000 = 100.0% 
Ramp time in seconds x 10, e.g. 250 = 25 seconds 
 
Low Byte = Drive Error Code, see table below 
High Byte = Drive Status as follows :‐ 
0 : Drive Stopped 
1: Drive Running 
2: Drive Tripped 
0..20000  Output frequency in Hz x10, e.g. 100 = 10.0Hz 
0..6000 
Output Motor Current in Amps x10, e.g. 10 = 1.0 Amps 
0..2000 
Output Motor Torque %x10, e.g. 1000 = 100.0% 
0..3200 
Output Motor Power in kW x10, e.g. 100 = 10.0kW 
0..15 
Indicates the status of the 4 digital inputs 
Lowest Bit = 1 Input 1 
0..1000 
Analog input % of full scale x10, e.g. 1000 = 100% 
0..1000 
Analog input % of full scale x10, e.g. 1000 = 100% 
0..1000 
DC Bus Voltage in Volts 
0..100 
Drive heatsink temperature in ºC 
0..660 
L1 – L2 Supply Voltage 
0..660 
L2 – L3 Supply Voltage 
0..660 
L3 – L1 Supply Voltage 
 
Internal Speed Value 
0..1000 
Energy consumed in kWh 
0..65535  Energy consumed in MWh 
Optidrive Plus 3
GV
 User Guide 