Setting Direct Connection Information - Omron NT - SUPPORT TOOL 07-1995 Operation Manual

Table of Contents

Advertisement

"Scr list" Screen
3-5-2

Setting Direct Connection Information

Procedure 1. Press the [F10] (Next) key on the "Screen List" screen.
42
The "Direct Spec. Setting" menu option on the "Screen List" screen allows batch
setting of the following functions:
S PT status control area allocation
S PT status notify area allocation
S Numeral table allocation and initial value setting
S Character-string table allocation and initial value setting
S Extended I/O unit input terminal allocation and function setting
S Extended I/O unit output terminal allocation
S Setting of the functions, display, and allocations of bit memory tables
WARNING
"Bit memory table" can only be selected when the NT
Model setting is NT30, NT30C, NT612G, or NT610C, and
the direct connection version used is Ver.3 or later.
Note
Be sure to allocate the data area referenced in the PC to the PT status control area
and PT status notify area. Allocate these two areas so that they do not overlap.
2. Press the [F2] (Direct) key.
3. Locate the bar cursor at the function to be set and press the
The function setting window will be displayed: carry out allocations to the data
area in the PC and function setting in this window. For details of the settings,
refer to the descriptions of the individual functions.
4. On completion of setting, press the [Esc] key.
Section 3-5
key.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nt-series support tool

Table of Contents