B.2 Parameter Table
No.
Name
d3-01 Jump Frequency 1 d3-01 to d3-04 allow programming of three prohibited frequency
d3-02 Jump Frequency 2
d3-04 Jump Frequency
Width
Frequency
d4-01
Reference Hold
Function Selection
<19> Range upper limit is dependent on parameters E1-04, Maximum Output Frequency, and d2-01, Frequency Reference Upper Limit.
<22> Parameter can be changed during run.
u

E: Motor Parameters

E parameters set V/f characteristics and motor-related data.
No.
Name
E1-01
Input Voltage
Setting
<24>
Max Output
E1-04
Frequency
E1-05
Max Output
<24>
Voltage
E1-06 Base Frequency
Mid Output
E1-07
Frequency
E1-08
Mid Output
<24>
Frequency Voltage
Minimum Output
E1-09
Freq.
E1-10
Minimum Output
<24>
Freq. Voltage
Motor Rated
E2-01
Current
E2-02 Motor Rated Slip Sets the motor rated slip in Hertz.
E2-03 Motor No-Load
Current
Motor
E2-05
Line-to-Line
Resistance
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<37> Setting range becomes 0.00 to 130.00 for drives 0.2 kW and smaller.
<57> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection.
174
Description
reference points for eliminating problems with resonant vibration
of the motor/machine. This feature does not eliminate the selected
frequency values, but accelerates and decelerates the motor through
the prohibited bandwidth.
The parameters must be according to the rule
d3-01 ≥ d3-02 .
This parameter sets the dead-band width around each selected
prohibited frequency reference point. The bandwidth becomes the
designated Jump frequency, plus or minus d3-04.
d4: Frequency Reference Hold
Use d4 parameters to configure the drive frequency reference hold function.
Determines if the frequency reference or frequency reference bias
is saved when the Run command is removed or the power goes off.
0: Disabled
1: Enabled
This parameter is effective when the multi-function inputs "Accel/
Decel Ramp Hold" or "Up/Down" commands are selected (H1-
 = A or 10/11).
Description
E1: V/f Pattern Characteristics
Use E1 parameters to set V/f characteristics for the motor.
This parameter must be set to the power supply voltage.
WARNING! Drive input voltage (not motor voltage) must be set
in E1-01 for the protective features of the drive to function properly.
failure to do so may result in equipment damage and/or death or
personal injury.
To set linear V/f characteristics, set the same values for E1-07 and
E1-09. In this case, the setting for E1-08 will be disregarded. Ensure
that the four frequencies are set according to these rules:
E1-04 ≥ E1-06> E1-07 ≥ E1-09
VACrms Out (V)
E1-05
E1-08
E1-10
E1-09
Use E2 parameters to set motor-related data.
Sets the motor nameplate full load current in amperes (A).
Sets the magnetizing current of the motor in Ampere.
Sets the phase-to-phase motor resistance in ohms.
E1-07 E1-06
E1-04
Frequency (Hz)
E2: Motor Parameters
Range
Def.
Mode
0.0 Hz
O
0.0 to 400.0
0.0 Hz
O
0.0 to 20.0 1.0 Hz
O
0, 1
0
O
Range
Def.
Mode
155 to 255
200
S
40.0 to
50 Hz
S
400.0
0.0 to 255.0 200 V
S
0.0 to
50 Hz
O
E1-04
0.0 to
2.5 Hz
O
E1-04
0.0 to 255.0 16.0 V
O
0.0 to
1.3 Hz
S
E1-04
0.0 to 255.0 12.0 V
O
10 to 200%
of drive
<57>
S
rated
current
0.00 to
<57>
O
20.00
0 to less
<57>
O
than E2-01
0.000 to
65.000
<57>
O
<37>
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Addr.
Pg.
Hex
294
84
295
84
297
84
298
84
Addr.
Pg.
Hex
300
86
303
86
304
86
305
86
306
86
307
86
308
86
309
86
30E
88
30F
88
310
88
312
88

Advertisement

Table of Contents
loading

Table of Contents