3.9 Main Frequency Reference

3.9

Main Frequency Reference

u

DIP Switch S1 Analog Input Signal Selection

The main frequency reference can either be a voltage or current signal input at terminal A1.
When using input A1 as a voltage input, set DIP switch S1 to "V" (right position, default setting) and program parameter
H3-01 to "0" (0 to +10 Vdc with lower limit) or "1" (0 to +10 Vdc without lower limit).
To use current input at terminal A1, set the DIP switch S1 to "I" and set parameter H3-01 = "2" or "3" (4-20 mA or 0-20
mA).
Voltage Input
0 to 10 V
Setting Value
V ( right position)
I ( left position)
No.
Parameter Name
Frequency ref. (voltage/
current)
H3-01
terminal A1 signal level
selection
46
Table 3.11 Frequency Reference Configurations
Drive
+10.5 V
+V
20 mA current
Main speed frequency
A1
reference (voltage input)
AC
Frequency reference
common
Figure 3.19 DIP Switch S1
Table 3.12 DIP Switch S1 Settings
Table 3.13 Parameter H3-01 Details
Description
Selects the signal level for terminal A1.
0: 0 to +10 V, unipolar input (negative frequency
reference values are zeroed)
1: 0 to +10 V, bipolar input (negative frequency reference
changes the direction)
2: 4 to 20 mA
3: 0 to 20 mA
4 to 20 mA input
or
0 to 20 mA input
DIP Switch S1
I
V
Description
Voltage input (0 to 10 V): default setting
Current input (4 to 20 mA or 0 to 20 mA)
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Current Input
Drive
+10.5 V
+V
20 mA current
Main speed
A1
frequency reference
(current input)
AC
Frequency
reference
common
Setting
Default
Range
Setting
0 to 3
0
MEMOBUS
Register
0