I/O Connections; I/O Connections; Sinking/Sourcing Mode Switch - Omron J1000 User Manual

J1000 series compact general purpose inverter
Hide thumbs Also See for J1000:
Table of Contents

Advertisement

3.8 I/O Connections

3.8

I/O Connections

u

Sinking/Sourcing Mode Switch

Set the DIP switch S3 on the front of the drive to switch the digital input terminal logic between sinking mode and sourcing
mode; the drive is preset to sinking mode.
Set Value
SINK
SOURCE
n
Transistor Input Signal Using 0 V Common/Sink Mode
When controlling the digital inputs by NPN transistors (0 V common/sinking mode), set the DIP switch S3 to SINK and
use the internal 24 V power supply.
n
Transistor Input Signal Using +24 V Common/Source Mode
When controlling digital inputs by PNP transistors (+24 V common/sourcing mode), set the DIP switch S3 to SOURCE
and use an external 24 V power supply.
44
Table 3.10 Sinking/Sourcing Mode Setting
Figure 3.16 DIP Switch S3
SOURCE
SINK
FWD Run/Stop
REV Run/Stop
External Fault N.O.
Fault Reset
Multi-step Speed 1
Figure 3.17 Sinking Mode: Sequence from NPN Transistor (0 V Common)
Details
Sinking Mode (0 V common): default setting
Sourcing Mode (+24 V common)
DIP Switch S3
SOURCE
SINK
Shielded Cable
S1
S2
S3
S4
S5
S3
SOURCE
SC
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
SINK
+24 V

Advertisement

Table of Contents
loading

Table of Contents