A.6 Drive Derating Data
A.6 Drive Derating Data
The drive can be operated at above rated temperature, altitude and default carrier frequency by derating the drive capacity.
u
Temperature Derating
As the ambient temperature for the drive is increased above the drive specification the drive should be derated. Additionally
parameter L8-35 Installation Method Selection on page
as illustrated in
Figure A.1
n
Output Current Derating Due to Ambient Temperature
If the ambient temperature is above the drive specification or if drives are side-by-side mounted in a cabinet, the parameters
L8-12 and L8-35 must be set according to the installation conditions. The output current is derated as shown in
A.1.
No.
Name
Ambient
L8-12
Temperature Setting
Installation Method
L8-35
Selection
168
on page 168.
Adjust the drive overload (oL2) protection level when the drive is installed
in an environment that exceeds its ambient temperature rating.
0: IP20/Open-Chassis Drive
1: Side-by-Side Mounting
2: NEMA Type 1 Drive
3: Finless Drive or External Heatsink Installation
100%
85%
80%
70%
Drive
Rating
50%
0
Figure A.1 Ambient Temperature and Installation Method Derating
168
should be set according to enclosure type and mounting method
Description
Parameter L8-35 = 0 (IP20/Open-Chassis Drive)
Parameter L8-35 = 3
(Finless Drive or External
Heatsink Installation)
Parameter L8-35 = 1
(Side-by-side Mounting)
Ambient tem p C
o
Parameter L8-12
o
o
o
30
35
40
50
-10 to 50
Parameter L8-35 = 2
(NEMA Type 1 Drive)
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Figure
Range
Def.
30 °C
0 to 3
0