C.12 Communication Errors
C.12 Communication Errors
u

MEMOBUS/Modbus Error Codes

A list of MEMOBUS/Modbus errors appears below.
When an error occurs, remove whatever caused the error and restart communications.
Error Code
Function Code Error
01H
• Attempted to set a function code from a PLC other than 03H, 08H, and 10H.
Register Number Error
02H
• A register number specified in the command message does not exist.
• Attempted to send a broadcast message using other register numbers than 0001H or 0002H.
Bit Count Error
• Read data or write data is greater than 16 bits. Invalid command message quantity.
03H
• In a write message, the "Number of Data Items" contained within the message does not equal twice the amount of data
words (i.e., the total of Data 1+ Data 2, etc.).
Data Setting Error
21H
• Control data or parameter write data is outside the allowable setting range.
• Attempted to write a contradictory parameter setting.
Write Mode Error
• Attempted to write while the drive was operating to a parameter that cannot be written to during run.
22H
• During an EEPROM data error (CPF06), the master attempted to write to a parameter other than A1-00 to -05, E1-03, or
o2-04.
• Attempted to write to read-only data.
DC Bus Undervoltage Write Error
23H
• Attempted to write from the master during an undervoltage fault (Uv1).
• Attempted to execute and Enter command during Uv1.
Write Error During Parameter Process
24H
• Master attempted writing to the drive while the drive was processing parameter data.
u

Slave Not Responding

In the following situations, the slave drive will ignore the command message sent from the master, and not send a response
message:
• When a communications error (overrun, framing, parity or CRC-16) is detected in the command message.
• When the slave address in the command message and the slave address in the drive do not match (remember to set the
slave address for the drive using H5-01).
• When the gap between two blocks (8 bit) of a message exceeds 24 bits.
• When the command message data length is invalid.
Note: If the slave address specified in the command message is 00H, all slaves execute the write function, but do not return response messages
to the master.
206
Error Name
Cause
SIEP C710606 33A OYMC AC Drive – J1000 User Manual