6.6 Operator Programming Errors

6.6

Operator Programming Errors

An Operator Programming Error (oPE) occurs when an inappropriate parameter is set or an individual parameter setting
is inappropriate.
The drive will not operate until the parameter is set correctly; however, no alarm or fault outputs will occur. If an oPE
occurs, investigate the cause and
action.
u

oPE Codes, Causes, and Possible Solutions

LED Operator Display
The drive capacity setting (o2-04) and the actual capacity of the drive are
not the same.
LED Operator Display
Parameters were set outside the possible setting range.
Note: Other errors are given precedence over oPE02 when multiple errors occur at the same time.
LED Operator Display
• The same function is assigned to two multi-function inputs.
• Excludes "Not used" and "External Fault."
The Up command was set but the Down command was not, or vice versa
(settings 10 vs. 11).
Run command for a 2-Wire sequence was set, but forward/reverse
command for a 2-Wire sequence was not.
The following two functions are set at the same time:
• Up/Down Command (10 vs. 11)
• Hold Accel/Decel Stop (A)
One of the following settings is set at the multi-function input terminals:
• External Search Command 1 and External Search Command 2 (61 vs.
62)
• Fast-Stop N.O. and Fast-Stop N.C.
(15 vs. 17)
LED Operator Display
Frequency reference is assigned to an option unit (b1-01 = 2 or 3) that is
not connected to the drive.
The Run command is assigned to serial communication (b1-02 = 2) but no
communication option is connected to the drive.
LED Operator Display
LED Operator Display
The following simultaneous contradictory settings: C6-05 is greater than
6 and C6-04 is greater than C6-03 (carrier frequency lower limit is greater
than the upper limit). If C6-05 is less than or equal to 6, the drive operates
at C6-03.
Upper and lower limits between C6-02 and C6-05 contradict each other.
132
Refer to oPE Codes, Causes, and Possible Solutions on page 132
Table 6.9 oPE Codes, Causes, and Possible Solutions
oPE01
Cause
oPE02
Cause
oPE03
Cause
oPE05
Cause
oPE10
Cause
oPE11
Cause
Drive Capacity Setting Fault
Drive capacity and then value set to o2-04 do not match.
Possible Solutions
Correct the value set to o2-04.
Parameter Range Setting Error
Possible Solutions
Set parameters to the proper values.
Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01
to H1-05.
Possible Solutions
• Ensure all multi-function inputs are assigned to different functions.
• Re-enter the multi-function settings to ensure this does not occur.
Correctly set functions that need to be enabled in combination with other
functions.
Correctly set functions that need to be enabled in combination with other
functions.
• Check if contradictory settings have been assigned to the multi-function
input terminals at the same time.
• Correct setting errors.
Run Command/Frequency Reference Source Selection Error
Possible Solutions
Reconnect the option unit to the drive.
V/f Data Setting Error
The following setting errors have occurred where: E1-04 is greater than
or equal to E1-06 is greater than or equal to E1-07 is greater than or equal
to E1-09.
Possible Solutions
Correct the settings for E1-04, -06, -07 and -09.
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
Possible Solutions
Correct the parameter settings.