3.2 Standard Connection Diagram

3.2

Standard Connection Diagram

Connect the drive and peripheral devices as shown in
without connecting digital I/O wiring. This section does not discuss drive operation;
Operation on page 51
for instructions on operating the drive.
NOTICE: Inadequate branch short circuit protection could result in damage to the drive. Install adequate branch circuit short circuit
protection per applicable codes. The drive is suitable for circuits capable of delivering not more than 30,000 RMS symmetrical amperes,
240 Vac maximum (200 V Class) and 480 Vac maximum (400 V Class).
NOTICE: When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters, pay special attention to the motor
insulation voltage or use a drive duty motor. Failure to comply could lead to motor insulation breakdown.
NOTICE: Do not connect AC control circuit ground to drive enclosure. Improper drive grounding can cause control circuit malfunction.
NOTICE: The minimum load for the multi-function relay output MA-MB-MC is 10 mA.
For single phase 200 V
power supply, use
R/L1 and S/L2.
R/L1
Three phase
power supply
S/L2
200 to 240 V
T/L3
2 MCCB THRX
Thermal relay for
motor cooling fan
MC
<1> Remove the jumper when installing an optional DC reactor.
<2> The MC on the input side of the main circuit should open when the thermal relay is triggered.
<3> Self-cooled motors do not require separate cooling fan motor wiring.
<4> Connected using sequence input signal (S1 to S5) from NPN transistor; Default: sink mode (0 V com).
<5> Use only a +24 V internal power supply in sinking mode; the source mode requires an external power supply
to I/O Connections on page
<6> Minimum load: 5 Vdc, 10 mA (reference value).
32
_
Terminals +1, +2, , B1, and B2
are for connecting options.
Never connect power supply
lines to these terminals.
2 MCCB
MC
1 MCCB
<4>
Forward run/stop
OFF ON MC
Reverse run/stop
SA
MC
THRX
External fault
SA
Fault reset
Multi-step
TRX
speed 1
main/aux switch
SA
TRX
MC MA
Fault relay
Digital inputs
(default setting)
2 k
Main speed
frequency
reference.
Multi-function
programmable
Figure 3.1 Drive Standard Connection Diagram (200 V Class Example)
44.
Figure
3.1. It is possible to run the drive via the digital operator
DC reactor
<1>
(option)
Thermal relay
(option)
<3>
Jumper
r1
-
+2
+1
B1
s1
J1000
t1
R/L1
Main circuit
S/L2
T/L3
Control circuit
S1
S2
S3
S4
S5
+ 24 V 8 mA
<5>
Sink
DIP
Source
switch S3
SC
Shield ground
terminal
Setting power supply
+V
+10.5 max. 20 mA
A1
0 to +10 V (20 k )
(0)4 to 20 mA (250 )
AC
shielded line
twisted-pair shielded line
control terminal
main circuit terminal
Refer to Start-Up Programming &
<2>
Braking resistor
(option)
Cooling fan
FU
r1
B2
FV
s1
FW
t1
U
U/T1
V
V/T2
W
W/T3
Ground
10
or less (400 V class)
Option unit
100
or less (200 V class)
connector
DIP switch S1
Digital output
250 Vac, 10 mA to 1 A
I
V
30 Vdc, 10 mA to 1 A
(default setting)
<6>
Fault
MA
MB
24 V
MC
Analog monitor
AM
+
output
AM
0 to +10 Vdc
AC
-
(2 mA)
Monitor
output
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Motor
M
M
<7>
Refer