C.7 Communications Timing
C.7 Communications Timing
To prevent overrun in the slave drive, the master should wait a certain time between sending messages to the same drive.
In the same way, the slave drive must wait before sending response messages to prevent an overrun in the master. This
section explains the message timing.
u

Command Messages from Master to Drive

In order to prevent overrun and data loss, the master must wait between receiving a response and sending the same type
of command as before to the same slave drive. The minimum wait time depends on the command as shown in the table
below.
Command Type
1
2
3
<1> If the drive receives command type 1 data during the minimum wait time, it will perform the command and then respond. However, if it receives
a command type 2 or 3 during that time, either a communication error will result or the command will be ignored.
A timer should be set in the master to check how long it takes for the slave drive(s) to respond to the master. If no response
is received within a certain amount of time, the master should try resending the message.
u

Response Messages from Drive to Master

If the drive receives a command from the master, it will process the data received and wait for the time set in H5-06 until
it responds. Increase H5-06 if the drive response causes overrun in the master.
194
Table C.2 Minimum Wait Time for Sending Messages
• Control command (Run, Stop)
• Set inputs/outputs
• Read monitors and parameter values
• Write parameters
• Save changes using an Enter command
PLC→Drive
Command message
Figure C.7 Minimum Wait Time for Sending Messages
PLC→Drive
Command message
24 bit length
Figure C.8 Minimum Response Wait Time
Example
Drive→PLC
Response message
24 bit length
Drive→PLC
Response message
H5-06
setting
Minimum Wait Time
50 ms
3 to 5 s
PLC→Drive
Command message
Time
Master Send
Wait Time
PLC→Drive
Command message
Time
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
10 ms
<1>
<1>