Operator Programming Errors (Ope) - Omron L7Z Quick Start Manual

Table of Contents

Advertisement

Displayed as
Display
Alarm
Fault
PUF
DC Bus Fuse
Open
RR
DynBrk Transistr
SE1
Sequence Error 1
SE2
Sequence Error 2
SE3
Sequence Error 3
SVE
Zero Servo Fault
UV1
(only in
DC Bus Under-
stop
volt
condi-
tion)
UV2
CTL PS Under-
volt

Operator Programming Errors (OPE)

An Operator Programming Error (OPE) occurs when two or more parameter related to each other are set inap-
propriate or an individual parameter setting is incorrect. The Inverter does not operate until the parameter set-
ting is set correctly; however, no other alarm or fault outputs will occur. If an OPE occurs, change the related
parameter by checking the cause shown in the table below. When an OPE error is displayed, press the ENTER
key to see U1-34 (OPE Detected). This monitor displays the parameter that is causing the OPE error.
Display
OPE01
Inverter kVA Setting Error
kVA Selection
Parameter Setting out of Range
Hiperface selected (n8-35=4) and:
• F1-01 is different from 512 or 1024
OPE02 Limit
• F1-21 is set to 2
EnDat selected (n8-35=5) and:
• F1-01 is different from 512 or 2048
• F1-21 is set to 0 or 1
Multi-function Input Selection Error (H1-01 to H1-05):
• Functions were selected duplicative.
• External Baseblock NO (8) and External Baseblock NC
OPE03
Terminal
(9) were selected at the same time.
The Emergency Stop Command NO (15) and NC(17) are
set simultaneously.
RUN/Reference Command Selection Error
OPE05
The Reference Source Selection b1-01 and/or the RUN
Sequence Select
Source Selection parameter b1-02 are set to 3 (option
board) but no option board is installed.
OPE06
Control method selection error /
PG Opt Missing
PG-card missing
OPE08
Function Selection Error
Constant Selection
OPE10
V/f Parameter Setting Error
V/f Ptrn Setting
Meaning
The fuse in the main circuit is blown.
Warning:
Never run the Inverter after replacing the DC bus
fuse without checking for shorted components.
The built-in dynamic braking transistor failed.
No output contactor response S1-16 or longer.
The output current at start was below 25% of no-load
current.
The output current during run was below 25% of no-
load current.
The motor position moved during Zero Servo Opera-
tion.
The DC bus voltage is below the under voltage
Detection Level
(L2-05). The default settings are:
200V class: 190 VDC
400 V class: 380 VDC
Main Circuit MC Operation Failure
No MC response during Inverter operation.
Control Power Supply Undervoltage
Undervoltage of the control circuit while the Inverter
was running.
Meaning
Corrective Actions
• Check the motor and the motor cables for short cir-
cuits or insulation failures (phase-to-phase).
• Replace the inverter after correcting the fault.
• Cycle power to the Inverter.
• Replace the Inverter.
Check the output contactor.
Check the output contactor.
Check the output contactor.
• Increase the torque limit.
• Decrease the load torque.
• Check for signal noise.
• Check the input voltage.
• Check the wiring of the input terminals.
• Check the input voltage and the wiring of the input
terminals.
• Extend the settings in
• C1-01/03/05/07
Replace the Inverter.
• Remove all connection to the control terminals and
cycle the power to the Inverter.
• Replace the Inverter.
Corrective Actions
Enter the correct kVA setting in o2-04.
Verify the parameter settings.
Verify the parameter settings in H1-
• Verify that the board is installed. Remove the power supply
and re-install the option board again
• Recheck the setting of b1-01 and b1-02.
Verify the control method selection in parameter A1-02 and/or
the installation of the PG option board.
Verify the control method and the function.
Check parameters (E1-
). A frequency/voltage value may
be set higher than the maximum frequency/voltage.
EN-26

Advertisement

Table of Contents
loading

Table of Contents