Timing Chart for Memory Operation
Sequence number
0000 Hex (0)
(word n+16, bit 00 to 15)
Sequence Number
Enable
(word n, bit 00)
START
(word n, bit 01)
Speed
Output pulses
Positioning Completed Flag
(word n+8, bit 05)
Busy Flag
(word n+8, bit 13)
Waiting For Memory
Operation Flag
(word n+8, bit 04)
Sequence number
(word I+58, bit 00 to 15)
Note
8-8-5

Timing of Data Changes during Memory Operation

220
Sequence
#1
Sequence
#0
0000 Hex
0002 Hex
0001 Hex
(0)
(0)
If START is turned from OFF to ON when the Sequence Number Enable Bit is
OFF after a power-up or a restart, the sequence number error (error code
8101) will be generated.
When START is re-executed while the Sequence Number Enable Bit is OFF,
the sequence numbers executed will be the same as those for INDEPEN-
DENT START.
It is possible to change positioning sequences and the data used in position-
ing sequences, such as speeds, positions, and acceleration times, during
memory operation. When performing positioning with the completion code set
to continuous, however, there will be a delay in the timing with which data
changes are reflected in operation.
When positioning sequences with completion codes set to continuous are
being executed continuously, the PCU reads up to 3 positioning sequences at
the start of memory operation. This means that if changes to data for a posi-
tioning sequence are not made during execution of the positioning sequence
at least 3 sequences before, these changes will not be reflected in operation.
Sequence
#2
Sequence
#3
0003 Hex
(2)
(3)
Section 8-8
Sequence
#4
Sequence
#0
0000 Hex
0001 Hex
0004 Hex
(4)
(0)
Sequence
#1
Time
0002 Hex
(0)