Omron CP1L CPU UNIT - 06-2007 Operation Manual page 592

Cp1l cpu unit
Table of Contents

Advertisement

Auxiliary Area Allocations by Address
Address
Name
Words
Bits
A406
All
PLC Setup
Error Location
A407
A407.00
Too Many I/O
to
Points, Details
A407.12
A407.13
Too Many I/O
to
Points, Cause
A407.15
A424
A424.00
Error Option
to
Board Flags
A424.15
A436
A436.00
CPM1A Unit
to
Error Flags
A436.02
A437
All
Number of
Connected
CPM1A Units
A438
All
Pulse Output
2 Stop Error
Code
A439
All
Pulse Output
3 Stop Error
Code
A440
All
Max. Interrupt
Task Process-
ing Time
Function
When there is a setting error in the
PLC Setup, the location of that error
is written to A406 in 4-digit hexadeci-
mal.
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash.
(A406 will be cleared when the
cause of the error is eliminated.)
Always 0000 hex.
The 3-digit binary value of these bits
indicates the cause of the Too Many
I/O Points Error.
Note These bits will be cleared
when the error is cleared.
The bit corresponding to the option
slot turns ON when an error occurs
in an Option Board (A315.13 will be
ON).
Bit 00: Option slot 1
Bit 01: Option slot 2
ON when an error occurs in a CP-
series Expansion Unit or Expansion
I/O Unit.
A436.00: 1st Unit
A436.10: 2nd Unit
A436.02: 3rd Unit
Stores the number of Expansion
Units and Expansion I/O Units con-
nected as a hexadecimal number.
Note This information is valid only
when a Too Many I/O Points
error has occurred. CP1W/
CPM1A-TS002 and CP1W/
CPM1A-TS102 are each
counted as two Units.
If a Pulse Output Stop Error occurs
for pulse output 2, the error code is
stored.
If a Pulse Output Stop Error occurs
for pulse output 3, the error code is
stored.
Contains the Maximum Interrupt
Task Processing Time in units of
0.1 ms.
(This value is written after the inter-
rupt task with the max. processing
time is executed and cleared when
PLC operation begins.)
Settings
Status
Status
after
at star-
mode
change
0000 to 01FF
Cleared
Cleared
hexadecimal
0000 hex
Cleared
Cleared
010: Too
Cleared
Cleared
many Expan-
sion Unit and
Expansion I/O
Unit words
011: Too
many Expan-
sion Units
and Expan-
sion I/O Units
ON: Error
Cleared
Cleared
OFF: No error
OFF: No error
Retained Cleared
ON: Error
0000 to 0007
Retained Cleared
hex
---
Retained Cleared
---
Retained Cleared
0000 to FFFF
Cleared
Cleared
hexadecimal
Appendix D
Write
Related
timing
flags, set-
tup
tings
Refreshed
A402.10
when error
occurs.
---
A401.11,
A407.13
to
A407.15
Refreshed
---
when error
occurs.
---
A353.13
---
---
---
---
Refreshed
---
when ori-
gin search
starts.
Refreshed
when a
pulse out-
put stop
error
occurs.
Refreshed
---
when ori-
gin search
starts.
Refreshed
when a
pulse out-
put stop
error
occurs.
See Func-
---
tion col-
umn.
559

Advertisement

Table of Contents
loading

Table of Contents