Error Classification and Confirmation
CPU Unit Indicators and Error Meanings in RUN or MONITOR Mode
Auxiliary Area
Indicator
CPU
error
POWER
Lit
RUN
Not lit
ERR/ALM
Lit
INH
Not lit
PRPHL
---
BKUP
---
■ Error Code Storage Word
The error code is stored in A400 when an error occurs. If two or more errors
occur at the same time, the most serious error will be stored.
■ Error Flags
Flags that indicate the type of error are allocated in the Auxiliary Area.
■ Error Information
This area indicates specific information on the meaning of error flags and pro-
vides information on error location and error details.
■ Fatal Errors
Error
Memory error
80F1
I/O bus error
80C0 to 80C7,
80CA, 80CE,
80CF
Too many I/O error 80E1
Program error
80F0
Cycle time too long
809F
error
FALS instruction
C101 to C2FF
executed
■ Non-fatal Errors
Error
FAL instruction
4101 to 42FF
executed
Flash memory
00F1
error
Interrupt task error 008B
PLC Setup error
009B
Option Board error 00D1, 00D2
Battery error
00F7
CPU
Fatal
Non-
standby
error
fatal
error
Lit
Lit
Lit
Not lit
Not lit
Lit
Not lit
Lit
Flashing ---
---
---
---
---
---
---
---
---
---
Error code
Error flag
(A400)
A401.15
A401.14
A401.11
A401.09
A401.08
A401.06
Error code
Error flag
(A400)
A402.15
A315.15
A402.13
A402.10
A315.13
A402.04
Section 9-1
Peripheral port
Output
communica-
OFF Bit
tions error
turned ON
Lit
Lit
Lit
Lit
---
---
Lit
Not lit
---
---
---
Error information
Meaning
Address
Memory error
A403
location
I/O bus error
A404
details
Details for too
A407
many I/O error
Program error
A294 to A299
details
---
---
---
---
Error information
Meaning
Address
Executed FAL
A360 to A391
number
---
---
Interrupt task
A426
error unit num-
ber
A406
Error Option
A424
Board Flags
---
---
477