Analog Adjuster And External Analog Setting Input - Omron CP1L CPU UNIT - 06-2007 Operation Manual

Cp1l cpu unit
Table of Contents

Advertisement

Analog Adjuster and External Analog Setting Input

6-4
Analog Adjuster and External Analog Setting Input
6-4-1
Analog Adjuster
Application Example
Note
6-4-2
External Analog Setting Input
External Analog Setting
Input Wiring
By turning the analog adjuster on the CP1L CPU Unit with a Phillips screw-
driver, the PV in the Auxiliary Area (A642) can be changed to any value within
a range of 0 to 255.
Phillips screwdriver
Analog adjuster
Setting the value for timer T100 in A642 makes it possible to use T100 as a
variable timer with a range of 0 to 25.5 s (0 to 255). A change in the set value
is reflected with the next scan.
Start input
T0100
Set values from the analog adjuster may vary with changes in the ambient
temperature and the power supply voltage. Do not use it for applications that
require highly precise set values.
When a voltage of 0 to 10 V is applied to the CP1L CPU Unit's external analog
setting input terminal, the voltage is converted from analog to digital and the
PV in A643 can be changed to any value within a range of 0 to 256 (0000 to
0100 hex).
External analog settings
input connector
Potentiometer, external
temperature sensor, etc.
0 to 10 V
Use the 1-m lead wire (included) for wiring to the external analog setting input
connector on the CP1L CPU Unit.
TIMX
0100
A642
100.00