Temperature Sensor Units
!Caution Set the temperature range according to the type of temperature sensor con-
!Caution Do not set the temperature range to any values other than those for which
Setting
Input type
0
K
1
2
J
3
4 to F
---
442
DIP Switch
Used to set the temperature
unit and the number of
decimal places used.
DIP Switch Settings
The DIP switch is used to set the temperature unit ( ° C or ° F) and the number
of decimal places used.
ON
1
2
SW1
1
Temperature unit
2
Number of decimal
places used (See note.)
(0.01 expression)
Note
For details on 2-decimal-place Mode, refer to Two-decimal-place Mode on
page 449.
Rotary Switch Setting
nected to the Unit. Temperature data will not be converted correctly if the tem-
perature range does not match the sensor.
temperature ranges are given in the following table. An incorrect setting may
cause operating errors.
The rotary switch is used to set the temperature range.
CP1W-TS001/TS002
CPM1A-TS001/002
Range (°C)
Range (°F)
−200 to 1,300
−300 to 2,300
0.0 to 500.0
0.0 to 900.0
−100 to 850
−100 to 1,500
0.0 to 400.0
0.0 to 750.0
Cannot be set.
Setting
°C
OFF
°F
ON
OFF
Normal (0 or 1 digit after the decimal
point, depending on the input range)
ON
2-decimal-place Mode
CP1W-TS101/TS102
CPM1A-TS101/102
Input type
Range (°C)
−200.0 to 650.0
Pt100
−200.0 to 650.0
JPt100
---
Cannot be set.
---
---
Section 7-5
Rotary Switch
Used to set the
temperature input range.
Temperature input terminals
Range (°F)
−300.0 to
1,200.0
−300.0 to
1,200.0