DeviceNet I/O Link Units
CPM1A-DRT21 DeviceNet I/O Link Unit
Number of I/O points
Number of words allocated in
CPU Unit I/O memory
Node number setting
Communications current con-
sumption
(5) Expansion I/O Connecting Cable
(1) DeviceNet Communications Connector
Used to connect DeviceNet communications. For the wiring, use the con-
nector provided with the CPM1A-DRT21 or use a connector purchased
separately.
(2) Rotary Switches (SW2, SW3)
Used to set DeviceNet node numbers.
Setting range: 0 to 63 (Do not set 64 to 99.)
(3) DIP Switch (SW1)
Used to set the DeviceNet baud rate and the output hold function.
Pin 1
Pin 2
OFF
OFF
125 kbps
ON
OFF
250 kbps
OFF
ON
500 kbps
ON
ON
Not allowed.
Pin 4
DeviceNet baud rate
OFF
Clears remote outputs when communications error occurs. (Outputs
turned OFF for each logic value.)
ON
Holds remote outputs when communications error occurs.
32 input points, 32 output points
2 input words, 2 output words
(Allocated in the same way as other Expansion Units
and Expansion I/O Units.)
Set using the rotary switches
(Set before turning ON the CPU Unit's power supply.)
48 mA
Baud rate setting (See note.)
Baud rate
500 m
250 m
100 m
---
Output hold function setting
Section 7-7
(2) Rotary Switches
(3) DIP Switch
(4) LED Indicators
(6) Expansion Connector
(1) DeviceNet Communications
Connector
Max. transmission path
length
461