I/O Memory Details - Omron CP1L CPU UNIT - 06-2007 Operation Manual

Cp1l cpu unit
Table of Contents

Advertisement

Specifications
Type
Model
Clock function
Memory
Built-in flash memory
Backup
Battery backup
Memory Cassette function
2-2-2

I/O Memory Details

Type
Model
CP1L-M40DR-A
CP1L-M40DR-D
CP1L-M40DT-D
CP1L-M40DT1-D
I/O
Input bits
24 bits
Areas
CIO 0.00 to CIO 0.11
CIO 1.00 to CIO 1.11
Output bits 16 bits
CIO 100.00 to
CIO 100.07
CIO 101.00 to
CIO 100.11
1:1 Link Bit
1,024 bits (64 words): CIO 3000.00 to CIO 3063.15 (words CIO 3000 to CIO 3063)
Area
Serial PLC
1,440 bits (90 words): CIO 3100.00 to CIO 3189.15 (words CIO 3100 to CIO 3189)
Link Area
Work bits
4,800 bits (300 words): CIO 1200.00 to CIO 1499.15 (words CIO 1200 to CIO 1499)
6,400 bits (400 words): CIO 1500.00 to CIO 1899.15 (words CIO 1500 to CIO 1899)
15,360 bits (960 words): CIO 2000.00 to CIO 2959.15 (words CIO 2000 to CIO 2959)
9,600 bits (600 words): CIO 3200.00 to CIO 3799.15 (words CIO 3200 to CIO 3799)
37,504 bits (2,344 words): CIO 3800.00 to CIO 6143.15 (words CIO 3800 to CIO 6143)
Work bits
8,192 bits (1,536 words): W000.00 to W511.15 (words W0 to W511)
TR Area
16 bits: TR0 to TR15
44
M CPU Units
CP1L-M40DR-A
CP1L-M40DR-D
CP1L-M40DT-D
CP1L-M40DT1-D
Supported.
Accuracy (monthly deviation): −4.5 min to −0.5 min (ambient temperature: 55°C),
User programs and parameters (such as the PLC Setup) are automatically saved to
the flash memory. It is also possible to save and read data memory initial data.
The data is automatically transferred to RAM when the power supply is turned ON.
(Data memory initial data, however, may or may not be transferred, depending on
the selection in the PLC Setup.
The HR Area, DM Area, and counter values (flags, PV) are backed up by a battery.
Battery model: CJ1W-BAT01 (Built into the CP1L CPU Unit.)
Maximum battery service life: 5 years
Guaranteed (ambient temperature: 55°C): 13,000 hours (approx. 1.5 years)
Effective value (ambient temperature: 25°C): 43,000 hours (approx. 5 years)
A CP1W-ME05M Memory Cassette (512K words, optional) can be mounted. It can
be used to back up the following data on the CPU Unit's RAM and to transfer the
data at startup.
• Data saved on Memory Cassette: User programs, parameters (such as the PLC
Setup), DM Area, data memory initial data, comment memory (CX-Programmer
conversion tables, comments, program indices), and FB program memory.
• Writing to Memory Cassette: By operations from the CX-Programmer.
• Reading from Memory Cassette: At startup, or by operations from the CX-Program-
mer.
Note
Can be used as Modbus-RTU easy master function.
M CPU Units
CP1L-M30DR-A
CP1L-M30DR-D
CP1L-M30DT-D
CP1L-M30DT1-D
18 bits
CIO 0.00 to CIO 0.11
CIO 1.00 to CIO 1.05
12 bits
CIO 100.00 to
CIO 100.07
CIO 101.00 to
CIO 100.03
CP1L-M30DR-A
CP1L-L20DR-A
CP1L-M30DR-D
CP1L-L20DR-D
CP1L-M30DT-D
CP1L-L20DT-D
CP1L-M30DT1-D
CP1L-L20DT1-D
−2.0 min to +2.0 min (ambient temperature: 25°C),
−2.5 min to +1.5 min (ambient temperature: 0°C)
CP1L-L20DR-A
CP1L-L20DR-D
CP1L-L20DT-D
CP1L-L20DT1-D
12 bits
CIO 0.00 to CIO 0.11
8 bits
CIO 100.00 to
CIO 100.07
Section 2-2
L CPU Units
CP1L-L14DR-A
CP1L-L14DR-D
CP1L-L14DT-D
CP1L-L14DT1-D
L CPU Units
CP1L-L14DR-A
CP1L-L14DR-D
CP1L-L14DT-D
CP1L-L14DT1-D
8 bits
CIO 0.00 to CIO 0.07
6 bits
CIO 100.00 to
CIO 100.05