3. Instructions
JMP0/JME0
Instruction
MULTIPLE JUMP
MULTIPLE JUMP END
Symbol
Applicable Program Areas
Function block
Area
definitions
Usage
OK
Flags
There are no flags affected by this instruction.
Function
When
the
execution
JMP0(515) is ON, no jump is made and
the program executed consecutively as
written.
When
the
execution
JMP0(515) is OFF, all instructions from
JMP0(515) to the next JME0(516) in the
program are processed as NOP(000).
Unlike
JMP(004),
CJPN(511), JMP0(515) does not use
jump numbers, so these instructions
can
be
placed
program.
198
Mnemonic
Variations
JMP0
---
JME0
---
JMP0
JMP0(515)
Block program areas
Step program areas
Not allowed
Not allowed
condition
for
condition
for
CJP(510),
and
anywhere
in
the
Function
code
When the execution condition for JMP0(515) is
515
OFF, all instructions from JMP0(515) to the next
JME0(516) in the program are processed as
516
NOP(000).
Subroutines
Interrupt tasks
OK
OK
Execution
Execution
condition a ON
condition a OFF
Instructions
executed
Execution
Execution
condition b ON
condition b OFF
Instructions
executed
Instructions jumped
CS/CJ/NSJ Series Instructions Reference Manual (W474)
Function
JME0
JME0(516)
SFC action or
transition programs
OK
Instructions
jumped
Jumped instructions
are processed as
NOP(000). Instruction
execution times are the
same as NOP(000).