Time And Interrupt Settings (Cx-Programmer Timings Tab Page) - Omron CJ - 08-2008 Operation Manual

Programmable controllers
Table of Contents

Advertisement

PLC Setup
7-1-2-3

Time and Interrupt Settings (CX-Programmer Timings Tab Page)

Enable Watch Cycle Time Setting
Programming
Console address
Word
Bit(s)
+209
15
0: Default
1: Bits 0 to 14
Default: 0
Watch Cycle Time
Programming
Console address
Word
Bit(s)
+209
0 to 14
001 to FA0: 10 to
40,000 ms
(10-ms units)
Default: 001 (1 s)
Cycle Time (Minimum Cycle Time)
Programming
Console address
Word
Bit(s)
+208
0 to 15
0001 to 7D00: 1 to
32,000 ms
(1-ms units)
Default: 0000
(No minimum)
294
Settings
Set to 1 to enable the Watch Cycle Time
Setting in bits 0 to 14. Leave this setting at 0
for a maximum cycle time of 1 s.
Settings
This setting is valid only when bit 15 of 209
is set to 1. The Cycle Time Too Long Flag
(A40108) will be turned ON if the cycle time
exceeds this setting.
Settings
Set to 0001 to 7D00 to specify a minimum
cycle time. If the cycle time is less than this
setting, it will be extended until this time
passes. Leave this setting at 0000 for a vari-
able cycle time. (Can't be changed during
operation.)
This cycle time will apply to the program
execution cycle when a parallel processing
mode is used.
Function
Function
Function
Section 7-1
Related
When set-
flags and
ting is read
words
by CPU Unit
A40108
At start of
(Cycle Time
operation.
Too Long
(Can't be
Flag)
changed dur-
ing opera-
tion.)
Related
When set-
flags and
ting is read
words
by CPU Unit
A264 and
At start of
A265
operation
(Present
(Can't be
Cycle Time)
changed dur-
ing opera-
tion.)
Related
When set-
flags and
ting is read
words
by CPU Unit
---
At start of
operation.