PLC Setup
Startup Hold Settings
Forced Status Hold Bit
Programming
Console address
Word
Bit(s)
+80
14
0: Cleared
1: Retained
Default: 0
IOM Hold Bit
Programming
Console address
Word
Bit(s)
+80
15
0: Cleared
1: Retained
Default: 0
Mode Setting
Programming
Console address
Word
Bit(s)
+81
---
Program (PRG):
PROGRAM mode
Monitor (MON):
MONITOR mode
Run (RUN): RUN
mode
Use programming
console (PRNC):
Programming Con-
sole's mode switch
Default: Use pro-
gramming console
Settings
This setting determines whether or not the
status of the Forced Status Hold Bit
(A50013) is retained at startup.
When you want all of the bits that have been
force-set or force-reset to retain their forced
status when the power is turned on, turn ON
the Forced Status Hold Bit and set this set-
ting to 1 (ON).
Settings
This setting determines whether or not the
status of the IOM Hold Bit (A50012) is
retained at startup.
When you want all of the data in I/O Memory
to be retained when the power is turned on,
turn ON the IOM Hold Bit and set this set-
ting to 1 (ON).
Settings
This setting determines whether the Startup
Mode will be the mode set on the Program-
ming Console's mode switch or the mode
set here in the PLC Setup.
Note If this setting is PRCN and a
Programming Console isn't
connected, startup mode will be
RUN mode.
Function
Function
Function
Section 7-1
Related
When set-
flags and
ting is read
words
by CPU Unit
A50013
At startup
(Forced Sta-
tus Hold Bit)
Related
When set-
flags and
ting is read
words
by CPU Unit
A50012 (IOM
At startup
Hold Bit)
Related
When set-
flags and
ting is read
words
by CPU Unit
---
At startup
289