PLC Setup
Baud Rate (bps)
Programming
Console address
Word
Bit(s)
+145
0 to 7
00: Standard
0A: High-speed NT
Link*
Default: 00
NT Link Max. (Maximum Unit Number in NT Link Mode
Programming
Console address
Word
Bit(s)
+150
0 to 3
0 to 7
Default: 0
Peripheral Bus Settings
Communications Setting
Programming
Console address
Word
Bit(s)
+144
15
0: Default (stan-
dard)*
1: PLC Setup (cus-
tom)
Default: 0
Mode: Communications Mode
Programming
Console address
Word
Bit(s)
+144
8 to 11
4: Peripheral bus
Default: 0
Baud Rate (bps)
Programming
Console address
Word
Bit(s)
+145
0 to 7
00: 9,600 bps
06: 9,600 bps
07: 19,200 bps
08: 38,400 bps
09: 57,600 bps
0A: 115,200 bps
Default: 00
Settings
* Set to 115,200 bps when setting this value
from the CX-Programmer.
Settings
This setting determines the highest unit
number of PT that can be connected to the
PLC in NT Link mode.
Settings
*The default settings are for a baud rate of
9,600 bps.
Settings
This setting determines whether the com-
munications mode for the peripheral port.
The Peripheral Bus Mode is used for all Pro-
gramming Devices except for Programming
Consoles.
Settings
The following settings are valid for the
Peripheral Bus Mode: 00 and 06 to 0A hex.
Function
)
Function
Function
Function
Function
Section 7-1
Related
When set-
flags and
ting is read
words
by CPU Unit
A61901
At the next
(Peripheral
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
Related
When set-
flags and
ting is read
words
by CPU Unit
A61901
At the next
(Peripheral
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
Related
When set-
flags and
ting is read
words
by CPU Unit
A61901
At the next
(Peripheral
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
Related
When set-
flags and
ting is read
words
by CPU Unit
A61901
At the next
(Peripheral
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
Related
When set-
flags and
ting is read
words
by CPU Unit
A61901
At the next
(Peripheral
cycle.
Port Settings
(Also can be
Changing
changed with
Flag)
STUP (237).)
309