Specifications of Basic I/O Units
Circuit Configuration
Terminal Connections
When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly
if the polarity is reversed.
Note Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on the Unit.
CJ1W-OD203 Transistor Output Unit (Terminal Block, 8 Points, Sinking)
Output
indicator
0
L
A0
2
L
A1
N C
12 to 24 V DC
A2
C O M 0
A3
N C
A4
4
A5
L
6
L
A6
N C
A7
12 to 24 V DC
C O M1
A8
Rated Voltage
Operating Load Voltage Range 10.2 to 26.4 V DC
Maximum Load Current
Maximum Inrush Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Insulation Resistance
Dielectric Strength
Number of Circuits
Internal Current Consumption
Fuse
External Power Supply
Weight
+V
O U T00
to
O U T03
C O M 0
+V
O U T04
to
O U T07
C O M 1
1
B0
L
3
L
B1
N C
B2
+V
B3
N C
B4
5
L
B5
7
B6
L
N C
B7
+V
B8
12 to 24 V DC
0.5 A/point, 4.0 A/Unit
4.0 A/point, 10 ms max.
0.1 mA max.
1.5 V max.
0.1 ms max.
0.8 ms max.
20 MΩ between the external terminals and the GR
terminal (100 V DC)
1,000 V AC between the external terminals and the
GR terminal for 1 minute at a leakage current of
10 mA max.
8 (8 points/common, 1 circuit)
5 V DC 100 mA max.
None
10.2 to 26.4 V DC, 20 mA min.
110 g max.
Appendix A
569