Name
Not Equal Flag
Less Than Flag
Less Than or Equal Flag
Negative Flag
Function
ZCP
ZCP(088) compares the 16-bit signed binary data in CD with the range defined by LL and UL and
outputs the result to the Greater Than, Equals, and Less Than Flags in the Auxiliary Area. (The Less
Than or Equal, Greater Than or Equal, and Not Equal Flags are left unchanged.)
When S > T2 as shown below, the > flag turns ON.
When T1
S
T2, the = flag turns ON. When S < T1, the < flag turns ON.
ZCP(088)Result
CD > UL
CD = UL
LL < CD < UL
CD = LL
CD < LL
ZCPL
ZCPL(116) compares the 32-bit signed binary data in CD+1, CD with the range defined by LL+1, LL
and UL+1, UL and outputs the result to the Greater Than, Equals, and Less Than Flags in the Auxiliary
Area. (The Less Than or Equal, Greater Than or Equal, and Not Equal Flags are left unchanged.)
When S+1,S > T2+1,T2 as shown below, the > flag turns ON.
When T1+1,T1
When S+1, S < T1+1, T1, the < flag turns ON.
ZCPL(116)Result
CD+1, CD > UL+1, UL
CD+1, CD = UL+1, UL
LL+1, LL < CD+1, CD <
UL+1, UL
CD+1, CD = LL+1, LL
CD+1, CD < LL+1, LL
CS/CJ/NSJ Series Instructions Reference Manual (W474)
Label
P_NE
• CJ2H (unit version 1.0 to 1.2), CS1-H, CJ1-H,
CJ1M, or CS1D CPU Unit: Held
• CJ2H (unit version 1.3 or later) or CJ2M CPU
Unit:
• ON if CD < LL.
• ON if CD > UL.
• OFF in all other cases.
P_LT
• ON if CD < LL.
• OFF in all other cases.
P_LE
• CJ2H (unit version 1.0 to 1.2), CS1-H, CJ1-H,
CJ1M, or CS1D CPU Unit: Held
• CJ2H (unit version 1.3 or later) or CJ2M CPU
Unit:
• ON if CD
UL.
• OFF in all other cases.
P_N
Held
Flag status
>
=
ON
OFF
OFF
ON
OFF
S+1, S
T2+1, T2, the = flag turns ON.
Flag status
>
=
ON
OFF
OFF
ON
OFF
Operation
ZCP
• CJ2H (unit version 1.0 to 1.2), CS1-H, CJ1-H,
• CJ2H (unit version 1.3 or later) or CJ2M CPU
• ON if CD+1, CD < LL+1, LL.
• OFF in all other cases.
• CJ2H (unit version 1.0 to 1.2), CS1-H, CJ1-H,
• CJ2H (unit version 1.3 or later) or CJ2M CPU
Held
<
OFF
ON
<
OFF
ON
3. Instructions
ZCPL
CJ1M, or CS1D CPU Unit: Held
Unit:
• ON if CD+1, CD < LL+1, LL.
• ON if CD+1, CD > UL+1, UL.
• OFF in all other cases.
CJ1M, or CS1D CPU Unit: Held
Unit:
• ON if LL+1, LL
CD+1, CD.
• OFF in all other cases.
3
277