TMUH/TMUHX

Instruction
HUNDREDTH-MS TIMER
BCD
Symbol
Applicable Program Areas
Function block
Area
definitions
Usage
OK
Operands
Operand
N
Timer Number
S
Set Value
N: Timer Number
The timer number must be between 0000 and 4095 (decimal).
S: Set Value
The set value must be between #0000 and 9999 (BCD).
&0 to 65535 decimal or #0000 to FFFF hex (Binary).
Operand Specifications
Word addresses
Area
CIO
WR
HR
N
---
---
---
S
OK
OK
OK
Flags
Name
Error Flag
Equals Flag
Negative Flag
CS/CJ/NSJ Series Instructions Reference Manual (W474)
Mnemonic
Variations
TMUH
---
TMUHX
---
TMUH
TMUH(541)
N
N: Timer number
S
S: Set value
Block program areas
Step program areas
Not allowed
OK
Description
AR
T
C
DM
EM
---
---
---
---
OK
OK
OK
OK
OK
Label
P_ER
• ON if timer number N is indirectly addressed through an Index Register but the address in the Index
Register is not the address of a timer's Completion Flag or PV.
• ON if in BCD mode and S does not contain BCD data.
• OFF in all other cases.
P_EQ
Unchanged
P_N
Unchanged
Function
code
544
TMUH(544)/TMUHX(557) operates a decrement-
ing timer with units of 0.01-ms.
557
Binary
Subroutines
OK
Data type
TMUH
TIMER
WORD
Indirect DM/EM
addresses
Con-
stants
@DM
*DM
DR
@EM
*EM
---
---
---
---
OK
OK
OK
OK
Operation
3. Instructions
Function
TMUHX
TMUHX(557)
N
N: Timer number
S
S: Set value
SFC action or transition
Interrupt tasks
programs
Not allowed
OK
Size
TMUHX
TIMER
1
UINT
1
Registers
Flags
Pulse
bits
Indirect
IR
TK
CF
using IR
---
OK
---
---
3
TR
bits
---
---
231