Operating Guide | iC7-Hybrid PROFINET
DISCHARGE TIME
The drive or power converter contains DC-link capacitors, which can remain charged even when the drive or power converter is
not powered. High voltage can be present even when the warning indicator lights are off. Failure to wait the specified time after
power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
l
Disconnect all power sources, including permanent magnet type motors.
l
Wait for capacitors to discharge fully. The discharge time is specified on the drive or power converter product label.
l
Measure the voltage level to verify full discharge.
l
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive or power converter properly can result in death or serious injury.
Ensure that the minimum size of the ground conductor complies with the local safety regulations for high touch current
l
equipment.
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment can result in death or serious injury.
Ensure that only trained and qualified personnel perform installation, start-up, and maintenance.
l
Ensure that electrical work conforms to national and local electrical codes.
l
Follow the procedures in this guide.
l
INTERNAL FAILURE HAZARD
An internal failure in the drive or power converter can result in serious injury when the drive or power converter is not properly
closed.
Ensure that all safety covers are in place and securely fastened before applying power.
l
Abbreviations
1.6
Table 1: Abbreviations
Abbreviation
CTW
DAP
DCP
DHCP
DO
DU
EMC
Danfoss Drives Oy © 2024.04
WARNING
NOTICE
WARNING
CAUTION
Definition
Control word
Device access point
Discovery and configuration protocol
Dynamic host configuration protocol
Drive object
Drive unit
Electromagnetic compatibility
AQ481922002453en-000101 / 172K4283A |
7