Start-up guide
IPS 8, CE, 230V AC, 1ph, 50Hz, code 084H5001
IPS 8, 230V AC, 1ph, 60Hz, code 084H5002

Advertisement

loading

Summary of Contents for Danfoss IPS 8

  • Page 1 Start-up guide IPS 8, CE, 230V AC, 1ph, 50Hz, code 084H5001 IPS 8, 230V AC, 1ph, 60Hz, code 084H5002...
  • Page 2: Table Of Contents

    User Guide | Intelligent Purging System (IPS 8) Ammonia Contents Mechanical / Refrigeration check ..................................3 Electrical check ........................................... 3 IPS controller (MCX15B2) setup ..................................4 IPS MCX controller – Quick start ..................................6 Lifting Procedure ........................................8 Connection points ........................................10 Installation ...........................................10...
  • Page 3: Mechanical / Refrigeration Check

    6) Remember to remove rubber plug. See Fig. 5. 7) Carry out proper vacuum on the purge point connect gas line and R717 side of IPS 8 purger. The R717 side of IPS 8 purger must be pressurized prior to the IPS 8 being put into operation.
  • Page 4: Ips Controller (Mcx15B2) Setup

    User Guide | Intelligent Purging System (IPS 8) Ammonia IPS controller (MCX15B2) After Mechanical / Refrigeration check, the conditions for startup must be checked. setup See Fig. 10 for overview of Electrical Panel and location of Thermal magnetic miniature circuit breakers 13) Switch ON: a.
  • Page 5 User Guide | Intelligent Purging System (IPS 8) Ammonia Go to Main Screen and watch compressor in operation and pressure/temperature changing. As compressor is in operation, pressure and temperature is changing, after about 15-25 minutes we should observe changes as reflected on below screens.
  • Page 6: Ips Mcx Controller - Quick Start

    User Guide | Intelligent Purging System (IPS 8) Ammonia IPS MCX controller – Quick Basically, the IPS with the built-in MCX controller, only need one setting, How many Purge points? start See steps below for how to navigate to the parameter for entering how many Purge points which is connected.
  • Page 7 User Guide | Intelligent Purging System (IPS 8) Ammonia IPS MCX controller – Quick It can be useful during commissioning to quickly move the next Purge point, in order not to wait to start IPS internal time cycle between purge points.
  • Page 8: Lifting Procedure

    User Guide | Intelligent Purging System (IPS 8) Ammonia Fig. 1 It is important that the support construction is level to ensure the internal liquid trap is properly filled. Angle to horizontal < 2 degrees Lifting Procedure All 4 lifting eyes must be positioned correctly, to match the actual used lifting gear All 4 lifting eyes must be used Fig.
  • Page 9 User Guide | Intelligent Purging System (IPS 8) Ammonia Min. 900 mm 1051 mm Min. 500 mm * For easy access to the main switch * For easy access to the main switch and servicing, the Purger unit shall be...
  • Page 10: Connection Points

    User Guide | Intelligent Purging System (IPS 8) Ammonia Connection points Be aware of liquid traps Where slope is shown above, ensure downward sloping pipe flowing towards purger drop leg. ICF 15-4 NH₃ gas + NC gases Purge Points - up to 8 points...
  • Page 11 User Guide | Intelligent Purging System (IPS 8) Ammonia Fig. 6a 11 | BC437120335698en-000101 © Danfoss | Climate Solutions | 2023.07...
  • Page 12 User Guide | Intelligent Purging System (IPS 8) Ammonia Solenoid coil to be connected in IPS Electrical panel to: Terminal Block: QG-XT2 Terminal numbers: 1 and 21: ICFD valve (DO6) ICF 20-4 with ICFD Fig. 6b Fig. 6C BC437120335698en-000101 | 12...
  • Page 13 User Guide | Intelligent Purging System (IPS 8) Ammonia Classified as Business fi fi fi Fig. 7a Controller box internal 13 | BC437120335698en-000101 © Danfoss | Climate Solutions | 2023.07...
  • Page 14 User Guide | Intelligent Purging System (IPS 8) Ammonia QM3 for see Fig. 8b Classified as Business fi fi fi Fig. 8a Controller box internal BC437120335698en-000101 | 14 © Danfoss | Climate Solutions | 2023.07...
  • Page 15 User Guide | Intelligent Purging System (IPS 8) Ammonia XT2 terminal block for field connected solenoids Terminal numbers: 1 and 2: ICFD valve (DO6) 3 and 4: Purge valve no. 1 (DO7) 5 and 6: Purge valve no. 2 (DO8) 7 and 8: Purge valve no.
  • Page 16 User Guide | Intelligent Purging System (IPS 8) Ammonia XT3 terminal block At different voltage for field connected solenoids coils: Remove connection between terminal: 1 and 3 2 and 4 Install transformer GD2 for supply of field connected solenoids coils.
  • Page 17 17 | BC437120335698en-000101 © Danfoss | Climate Solutions | 2023.07...