User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Introduction The Danfoss Intelligent Purger System (IPS 8) independent of the main ammonia system and is a stand-alone, self-contained purging unit with only one flange connection to the ammonia designed to remove non-condensable gases plant.
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Working principle The Danfoss IPS 8 is factory-tested and ready for By condensing the ammonia gas, a new use in ammonia plants with a condenser pressure ammonia/NC gases mix is naturally pulled of more than 6 bar (87 psi).
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Working cycle The Danfoss IPS 8 operates in 24-hour cycles, of this to be a high concentration of NC gases which 45 minutes are dedicated to a R452A pull and opens the purge solenoid valve.
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Connection locations Air purger installation in a low-pressure liquid level controlled installation The correct locations for the air purger to be any given time. Otherwise the liquid column in connected to the ammonia plant are: the condenser will be short-circuited.
Page 9
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Connection locations Air purger installation in a high-pressure liquid level controlled installation (continued) The float valve (3) will flash any liquid back to For systems with a high-pressure liquid level the LP side.
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Connection points Single point or multi-point purging Single point purging is the basic setup in the NEVER HAVE MORE THAN 1 POINT OPEN AT A TIME.
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Installation The Danfoss IPS 8 should be installed in Use all 4 lifting eyes and appropriate lifting gear accordance with locations recommended in the during installation (unit weight 100 kg/220 lbs).
Page 12
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Installation (continued) 416,4 Enclosed gasket Enclosed bolts, Torque: 60 Nm (44.3 ft lb) diagonal tension Enclosed weld flange (fig. 14) Purging pipe OD 17.2 for rubber hose to water bath Do not unscrew restrictor inside pipe.
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Electrical wiring The internal wiring of the purger is done at the It is recommended to protect all external cables factory. Only the electrical wiring for the main...
Page 14
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Electrical wiring (continued) 230V AC Press. Switch Compressor Condenser Extraction Crankcase Power supply Power supply air fan heater MCX15B Solenoid valves* *By useof GD2 24V DC remove 1-2 and 3-4 bridges between the terminals and connect power supply Fig.
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Electrical wiring (continued) 24V DC 24V DC R717 High Discharge Suction Temp. pressure pressure Temp. sensor Temp. sensor sensor sensor sensor 0V DC 0V DC...
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Display After switching on the controller, a display While in operation mode, the Up/Down arrows window will momentarily show the actual lead to the status windows mentioned in the software version, followed by the default main table below.
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Programming/Configuration By pressing the main menu will show up with below options Main Menu Submenu Submenu/status Submenu/status Default Description Label No alarm Active alarms...
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Maintenance/Service/ Maintenance minimum once per year Disposal Use P&I dagram and check that all powered components is working properly Check for alarms in the MCX controller...
User Guide | Intelligent Purger System (IPS 8) for Ammonia - Technical data, installation and use Technical data Supply voltage 230V AC, 1ph, 50Hz Current 5.7 A (max. 6.5 A) Power consumption max. 1.3 kW Short-circuit current rating Icc 10kA Temperature range ambient -10 °C to +43 °C (14 °F to 109 °F)
Need help?
Do you have a question about the IPS 8 and is the answer not in the manual?
Questions and answers