Please consult the operating instructions or online help for details on using SIMATIC PDM.
1. If you have not already done so, check that you have the most up-to-date Electronic Device
Description (EDD) for your device. [See Configuring a new device (Page 94).]
2. Launch SIMATIC Manager and create a new project. Application examples for setting up HART
and PROFIBUS PA devices with SIMATIC PDM can be downloaded from the Product page of
our website:
Product page (www.siemens.com/LR500)
8.6.1.6

Quick start note

Quick start
Note
• A reset to Factory Defaults should be performed before running the Quick Start Wizard if
device has been used in a previous application. See Master Reset via SIMATIC PDM
(Page 105).
• The Quick Start wizard settings are inter-related and changes apply only after you click
on FINISH AND DOWNLOAD at the end of the last step to save settings offline and transfer
them to the device.
• Do not use the Quick Start Wizard to modify individual parameters: for quick access to echo
profile parameters, see Echo Profile via SIMATIC PDM (Page 207) or see Parameter Reference
(Page 113) for a complete list. (Perform customization only after the Quick Start has been
completed.)
• Click on BACK to return and revise settings or CANCEL to exit the Quick Start.
• For a vessel with obstructions see Auto False Echo Suppression via SIMATIC PDM (Page 98).
8.6.1.7

Quick start menu and instruction

Launch SIMATIC PDM, open the menu Device – Wizard - Quick Start, and follow steps 1 to 4.
SITRANS LR500 series with mA/HART
Operating Instructions, 03/2024, A5E51099898-AA
1
Quick start wizard
Operating