6.2.3.1

Quick Start Wizard via the handheld programmer

Note
• A reset to factory defaults should be performed before running the Quick Start Wizard if
the device has been used in a previous application. See Master Reset (4.1.).
• The Quick Start wizard settings are inter-related and changes apply only after you select
Finish in the Wizard Complete step.
• Do not use the Quick Start wizard to modify parameters: see instead Parameter
Reference (Page 113). (Perform customization for your application only after the Quick
Start has been completed).
• Default settings in the parameter tables are indicated with an asterisk (*).
1. Quick Start
1.1. Quick Start Wiz
● Point the programmer at the display from a maximum distance of 300 mm (1 ft), then
press RIGHT arrow
● Press RIGHT arrow
● Press RIGHT arrow
move directly to the next item.
● To change a setting, scroll to the desired item or key in a new value.
● After modifying a value, press RIGHT arrow
to move to the next item.
● Quick Start settings take effect only after you select Finish.
Material
Selects the appropriate echo processing algorithms for the material [see Position Detect
(2.8.4.2.) for more detail].
Options
dK < 3.0
a)
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
to activate PROGRAM mode and open menu level 1.
twice to navigate to menu item 1.1 and open parameter view.
to open Edit mode or DOWN arrow to accept default values and
*
LIQUID
LIQUID LOW DK
(low dielectric liquid – CLEF algorithm enabled)
a)
6.2 Operating via the handheld programmer
to accept it and press DOWN arrow
Commissioning