9.3.3.2

Echo configuration (3.3.2)

Near range (3.3.2.1)
Sets minimum distance from sensor reference point, beyond which an echo should be
considered valid.
This is sometimes referred to as blanking or a dead zone.
Setting
Default
Far range (3.3.2.2)
Sets maximum distance from sensor reference point, within which an echo should be
considered valid.
Use this feature if the measured surface can drop below the lower calibration point in normal
operation.
Setting
Default
9.3.3.3

Echo select (3.3.3)

Algorithm (3.3.3.1)
Sets algorithm (applied to the echo profile) to extract the true echo.
Setting
Default
Echo threshold (3.3.3.2)
Sets minimum echo confidence. Only echoes above this threshold are evaluated.
Setting
Default
Position detect (3.3.3.3)
Sets algorithm used to calculate the position of the echo.
SITRANS LR500 series with mA/HART
Operating Instructions, 03/2024, A5E51099898-AA
0 to 126 m
0 m
0 to 126 m
32 m
First echo
Largest echo
Echo area
Best echo of the first and largest echo
Area largest first echo
True first echo
First echo
-20 to 70
1 to 70
Parameter assignment
9.3 Maintenance and diagnostics (3)
F
L
A
BLF
ALF
TF
F
133