1.13 Sealing Cabinets

If the unit will not be powered on after installation, take dustproof and anti-
condensation measures (for example, use a dust cover, plastic film, or fabric cloth)
to prevent condensation and dust buildup, which may corrode the unit. Remove
the protective objects when the unit needs to be used.
Step 1 Ensure that all items have been checked after the installation.
Step 2 Fill in gaps between the cables and the cabinets with sealing putty.
1.
2.
Issue 01 (2023-03-20)
Check Item
Foreign matter cleaning
inside the cabinets
Air filters on the front
doors of cabinets
NO TICE
Remove the paper protective film from the sealing putty and keep the
transparent film.
Fill the gaps between the cables and the cabinets with the sealing putty.
Ensure that the transparent film faces upward.
Copyright © Huawei Technologies Co., Ltd.
1 Installation and Cable Connection
Acceptance Criteria
The inside and outside of the cabinets
are free from conductive dust or other
foreign matter.
1. There is no foreign matter (such as
copper wires and screws) on the top
of the cabinets.
2. There is no foreign matter on the
copper bar terminals.
3. There is no foreign matter around
switch terminals.
4. There is no foreign matter on the
bottom plates of the cabinets.
5. There is no foreign matter on the rear
module subracks.
The air filters on the front doors of the
cabinets are intact. Any damaged air
filter should be replaced promptly.
Removing an air filter will compromise
the equipment performance, which may
result in equipment damage.
71