Other Optional Components - Huawei UPS5000-H-800 kVA-NTN Quick Manual

Table of Contents

Advertisement

UPS5000-H-800 kVA-NTN
Quick Guide (480 V, 100 kVA Power Modules)
Capacity
500 kVA
400 kVA
300 kVA
200 kVA

1.2.5 Other Optional Components

Cables for the Dry Contact Card
Table 1-4 Cables for the dry contact card
Name
Specifications
Cable
Double-insulated twisted cable. If the
cable length is within 25–50 m, the
cross-sectional area must be 0.5–1.5
mm
Cables for the Monitoring Interface Card
Table 1-5 Cables for the monitoring interface card
Name
Specifications
RS485 cable/FE
Shielded cables are required.
cable
Cable
Double-insulated twisted cable. If the
cable length is within 25–50 m, the
cross-sectional area must be 0.5–1.5
mm
Issue 01 (2023-03-20)
Mains Input
Bypass Input
Circuit Breaker
Circuit Breaker
Specifications
Specifications
800 A/3P
800 A/3P
630 A/3P
500 A/3P
500 A/3P
400 A/3P
320 A/3P
250 A/3P
2
.
2
.
Copyright © Huawei Technologies Co., Ltd.
1 Installation and Cable Connection
Downstream
Output Circuit
Breaker
Specifications
800 A/3P
500 A/3P
400 A/3P
250 A/3P
Quantity (PCS)
Remarks
Several
Provided by the
customer
Quantity (PCS)
Remarks
Several
Provided by the
customer
Several
Provided by the
customer
Maintenance
Bypass Circuit
Breaker
Specifications
800 A/3P
500 A/3P
400 A/3P
250 A/3P
11